1.2RTD Input to Digital Conversion

Engineering Units The following equations may be used to calculate the digital word in decimal format which will result from a particular RTD input:

RTD Mode, Digital Word (WX) = Degrees X 10

Millivolt Mode, Digital Word (WX) = Millivolts X 100

As an example, the following figure illustrates the effects of a change in input level going from 0 degrees to 102.4 degrees in the RTD Input Mode.

 

Figure 1-2 Example Change Input Level

Scale Units

When data format is selected as SCALE the full temperature range of the

 

RTD is scaled as an unsigned integer from 0±32000. The following formula

 

may be used to calculate the scaled integer value:

 

Scaled Integer = (measured temp ± min temp) ⎟(max temp ± min temp) ⋅

 

32000

 

For example the scaled integer offset at 0_C for a 100 Pt RTD is:

 

Scaled Integer = 0 ± (±199.8) ⎟(849 ± (±199.8)) ⋅ 32000 = 6091

1-4

Description

SIMATIC 505±2557 Installation and Operation Guide

Page 14
Image 14
Siemens 505-2557 installation and operation guide RTD Input to Digital Conversion, Scale Units