Output Registers The SIMATIC 505±2557 module also utilizes 32 WY registers. These registers are used to transfer the scaling values, the alarm setpoints, the filtering time constants, and the averaging count values to each of the sixteen channels.
After the data is loaded into the module, these registers then enable each of the functions on a
Table 3-4 Output Data Registers
| WY65 | Channel 1 | Low alarm setpoint | |
| . |
|
| |
| . |
|
| |
Alarms | WY80 | Channel 16 | Low alarm setpoint | |
WY81 | Channel 1 | High alarm setpoint | ||
| ||||
| . |
|
| |
| . |
|
| |
| WY96 | Channel 16 | High alarm setpoint | |
|
|
|
| |
| WY65 | Channel 1 | Scaling low setpoint | |
| . |
|
| |
| . | Channel 16 |
| |
Scaling | WY80 | Scaling low setpoint | ||
WY81 | Channel 1 | Scaling high setpoint | ||
| ||||
| . |
|
| |
| . | Channel 16 |
| |
| WY96 | Scaling high setpoint | ||
|
|
|
| |
| WY65 | Channel 1 | Settling time | |
Digital Filtering | . |
|
| |
. |
|
| ||
| Channel 16 | Settling time | ||
| WY80 | |||
|
|
|
| |
| WY81 | Channel 1 | Average sample counts | |
Averaging | . |
|
| |
. |
|
| ||
|
|
| ||
| WY96 | Channel 16 | Average sample counts | |
|
|
|
|
SIMATIC 505±2557 Installation and Operation Guide | Advanced Function Programming |