Configuring the | The SIMATIC 505±2557 must be configured for 10 Ohm copper, 100 Ohm | |
Module | platinum or 120 Ohm nickel RTDs (2, 3 or 4 wire) or millivolt range and | |
| digital filtering/no filtering mode before wiring the input connectors and | |
| inserting the module into the I/O base. | |
|
| |
| NOTE: As shipped, all input channels are configured 100 Ohm platinum, 3 | |
| wire RTDs, degrees Centigrade and digital filtering enabled. | |
|
| |
| Configuring the module is a two step process. Hardware jumpers are | |
| positioned to provide proper gain and lead wire compensation for either 3 | |
| wire or 4 wire RTDs. DIP switches are provided to inform the | |
| microprocessor the changes made to the hardware. | |
| Changing the module input channel configuration involves the following | |
| steps: | |
| 1. | Selecting temperature or millivolt measurement via DIP switch |
| 2. | Selecting 3 or 4 wire compensation |
| 3. | Selecting 100 Ohm platinum, 120 Ohm nickel or 10 Ohm copper input |
|
| mode for each channel |
| 4. | Selecting standard login mode (16WX) or Advanced Operating Mode |
| 5. | Selecting digital filtering or no filtering for the module |
| 6. | Selecting degrees C or F for the module |
| 7. | Selecting Engr units or SCALE units for module |
| 8. | Logging the configuration jumper settings for future reference |
| Each of these steps is described in the following sections. |
SIMATIC 505±2557 Installation and Operation Guide | Installation |