3 Installation and Commissioning
| Slider for setting | Attachment to Industrial |
| Ethernet: | |
| the chassis | 2 x |
| ground contact | |
Figure | Connectors of a CP 343−1 Lean with the Front Panel Open |
|
Ground/Chassis Ground Concept
Notice
Please note the instructions regarding the grounding and chassis ground concept in the SIMATIC S7 installation guides; see “SIMATIC S7 Programmable Controller S7−300 − Installation and Hardware: Installation Manual” /1/.
Behind the hinged panel on the left of the device, you will see a slider with which you can connect or disconnect the chassis ground of the 24 V power supply with reference ground.
SSlider pushed in: chassis and reference ground connected (note: the slider must be felt to lock in place).
SSlider pulled out: No connection between chassis and reference ground. When shipped: Slider pushed in
Use a screwdriver to set the slider.
Note
An Ethernet cable can also be inserted and removed with the power supply on.
B3L−12 | CP |
Release 03/2007 |