5 Performance Data

5 Performance Data

5.1Number of Possible Connections over Ethernet

Table 5-1

Characteristic

Explanation / Values

Permitted number of simultaneous connections in total over Industrial Ethernet

12 maximum

Example of Maximum Load

You can operate:

4 S7 connections

4 ISO-on-TCP connections

2 TCP connections

2 UDP connections Also:

SFurther TCP connections for Web diagnostics

S1 PROFINET connection to a PROFINET IO controller

5.2Characteristic Data for S7 Communication

Table 5-2

Characteristic

Explanation / Values

 

 

Number of connections for S7 communication on

4 maximum

Industrial Ethernet for

(the number depends on the CPU type being used.

 

 

S Operator control and monitoring functions (HMI)

Please refer to /1/ for the values for your CPU.)

S S7 connections configured at one end

 

 

 

LAN interface − data record length per protocol unit

 

S

sending

240 bytes / PDU

S

receiving

240 bytes / PDU

 

 

 

 

 

CP 343-1 Lean for Industrial Ethernet / Manual Part B3L