6 Configuring and Programming the CP as a PROFINET IO Device

6.3.2Assigning the PROFINET IO Device to a PROFINET IO Controller

PROFINET IO Controller

This section describes the configuration of PROFINET IO controllers with STEP 7. This includes:

SStations of the type SIMATIC 300 and SIMATIC 400

CPU with integrated PROFINET IO controller (for example CPU 317−2 PN/DP).

CPU with external PROFINET IO controller (for example CP 343−1).

SSIMATIC PC station

For example with CP 1616

If you do not configure your system with STEP 7, you will need to use the GSDML file of the CP to configure the CP in your configuration system (download address see Section 9.10)

When configuring the PROFINET IO device (see Section 6.3.1), the selected PROFINET IO controller is unimportant.

Requirements for Configuration in STEP 7

There must be a SIMATIC station in the STEP 7 project in which a module (CPU or CP) supports operation as PROFINET IO controller.

Notice

The IP address of the PROFINET IO device and the IP address of the PROFINET IO controller must be located in the same IP subnet.

Step 1: Configuring the PROFINET IO controller

With some PROFINET IO controller types, STEP 7 automatically creates a PROFINET IO system as soon as you insert the module, otherwise you may need to add a PROFINET IO system. Drag the required IO devices from the hardware catalog to this PROFINET IO system.

Configure a PROFINET IO controller as follows:

1.Open the hardware configuration of the station you want as PROFINET IO controller in HW Config.

2.If no PROFINET IO system exists, select the PROFINET IO controller (for example CP 343−1 EX30/GX21, CP 443−1 EX41, CPU 317−2 PN/DP) and insert a PROFINET IO system (menu “Insert” "“PROFINET IO System”).

B3L−24

CP 343-1 Lean for Industrial Ethernet / Manual Part B3L