3 Installation and Commissioning

!

!

Note

The hinged front panel must be kept closed during operation.

The module must be installed so that its upper and lower ventilation slits are not covered, allowing adequate ventilation.

Warning

When used under hazardous conditions (zone 2), the devices must be installed in an enclosure.

To comply with ATEX100a (EN 60079−15), this enclosure must meet the requirements of at least IP54 in compliance with EN 60529.

WARNING − EXPLOSION HAZARD: DO NOT DISCONNECT EQUIPMENT WHEN A FLAMMABLE OR COMBUSTIBLE ATMOSPHERE IS PRESENT.

Warning

The device is designed for operation with safety extra-low voltage (SELV). This means that only safety extra-low voltages (SELV) complying with IEC950/EN60950/ VDE0805 may be connected to the power supply terminals.

The power unit for supplying the device must comply with NEC Class 2 as described by the National Electrical Code(r) (ANSI/NFPA 70).

The power of all connected power units in total must correspond to a limited power source (LPS).

CP 343-1 Lean for Industrial Ethernet / Manual Part B3L

B3L−13

Release 03/2007

C79000-G8976-C198-04

Page 13
Image 13
Siemens CP 343-1 manual B3L−13