5 Performance Data

5.4Characteristic Data for PROFINET IO

CP as PROFINET IO device

The CP supports the following maximum configuration as a PROFINET IO device:

Table 5-5

 

Characteristic

Explanation / Values

 

 

Size of the input area of the PROFINET IO device

512 bytes max.

 

 

Size of the output area of the PROFINET IO device

512 bytes max.

 

 

Size of the IO data area per submodule in a PROFINET IO device

 

S

Inputs

240 bytes

S

Outputs

240 bytes

 

 

Size of the consistency area for a submodule

240 bytes

 

 

Maximum number of submodules

32

 

 

 

Execution times of the FCs PNIO_SEND / PNIO_RECV

The calculation of the reaction times with PROFINET IO is determined by the execution time of the function blocks required on the S7-300 CPU (PNIO_SEND, PNIO_RECV).

Table 5-6

Component

Explanation / Values

 

 

 

Execution time on the CPU

per PNIO_SEND block call:

per PNIO_RECV block call:

315−2DP

S < 1 ms at 240 bytes

S < 1 ms at 240 bytes

(6ES7 315−2EG10−0AB0)

 

 

 

 

 

Execution time on the CPU

per PNIO_SEND block call:

per PNIO_RECV block call:

317−2PN/DP

S < 0.8 ms at 240 bytes

S < 0.8 ms at 240 bytes

(6ES7 317−2EJ10−0AB0)

 

 

 

 

 