Power Supply Modules

3-27

S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
Technical Specifications of the PS 407 20 A
Programming Package
Associated programming
package As of STEP7 V 2.0
Dimensions, Weight, and Cable Cross-Sections
Dimensions WxHxD (mm)
Weight
Cable cross-section
75x290x217
1.93 kg
3x1.5 mm 2 (litz wire
with wire end ferrule
with wire end ferrule
with insulating collar;
use only flexible
sheath cable)
Cable diameter 3 to 9 mm
Input Rating
Input voltage
Rated value
Permitted range
120/230 VAC
85 to 132 VAC /
170 to 264 VAC
System frequency
Rated value
Permitted range
50 / 60 Hz
47 to 63 Hz
Rated input current
At 120 VAC
At 230 VAC
1.87 A
1 A
Starting current inrush
Rated input current 264 V
Rated input current 132 V
Peak value 70 A
Half-value width 2 ms
Peak value + 110 A/ –
65 A
Half-value width
1.5 ms
Leakage current < 3.5 mA
Overvoltage resistance In accordance with DIN
VDE 0160, curve W2
Output Rating
Output voltages
Rated values 5.1 VDC /24 VDC
Output currents
Rated values 5 VDC: 20 A
24 VDC: 1.0 A
Max. residual ripple 5 VDC: 50 mVSS
24 VDC: 200 mVSS
Max. switching peaks 5 VDC: 150 mVS
24 VDC: 500 mVS
Idle conditions 5 VDC: 200 mA base
load required
24 VDC: Idling-proof
(no base load required)
Other Parameters
Protection class in accordance
with IEC 60536 I, with protective
grounding conductor
Overvoltage category II
Pollution severity 2
Rated voltage Ue
0 < Ue 50 V
150 V < Ue 300 V
Test Voltage
700 VDC
(secondary <–> PE)
2200 VDC
(primary <–> PE)
Buffering of power failures:
At 50 Hz
At 60 Hz 4.5 ms to 7.5 ms
6.5 ms to 8.5 ms
Power input 162 W
Power loss 35.6 W
Backup current Max. 100 µA at power
off
Backup batteries (optional) 2 x Lithium AA, 3.6 V /
1.9 Ah
Protective separation
to IEC 61131-2 Yes