Power Supply Modules

3-29

S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
Polarity Reversal of L+ and L-

The polarity reversal of L+ and L- with supply voltages of between 88 VDC

and 300 VDC has no effect on the function of the power supply. The connection

should be made as described in the instructions in the Installation Manual,

Chapter 6.

Technical Specifications of the PS 407 20 A
Dimensions, Weight, and Cable Cross-Sections
Dimensions WxHxD (mm)
Weight
Cable cross-section
75x290x217
2.2 kg
3x1.5 mm 2 (litz wire
ith ire end ferr le
with wire end ferrule
with insulating collar;
use only flexible
sheath cable)
Cable diameter 3 to 9 mm
Input Rating
Input voltage
Rated value
Permitted range
110/230 VDC
120/230 VAC
88 to 300 VDC,
85 to 264 VAC
(long-range input)
System frequency
Rated value
Permitted range
50 / 60 Hz
47 to 63 Hz
Rated input current
At 120 VAC / 110 VDC
At 230 VAC / 230 VDC
1.5 A
0.8 A
Starting current inrush Peak value 88 A
half-value width 1.1 ms
Leakage current < 3.5 mA
Overvoltage resistance In accordance with DIN
VDE 0160, curve W2
Output Rating
Output voltages
Rated values 5.1 VDC /24 VDC
Output currents
Rated values 5 VDC: 20 A
24 VDC: 1.0 A
Max. residual ripple 5 VDC: 50 mVSS
24 VDC: 200 mVSS
Max. switching peaks 5 VDC: 150 mVS
24 VDC: 500 mVS
Idle conditions 5 VDC: 200 mA base
load required
24 VDC: Idling-proof
(no base load required)
Other Parameters
Protection class in accordance
with IEC 60536 I, with protective
grounding conductor
Overvoltage category II
Pollution severity 2
Rated voltage Ue
0 < Ue 50 V
150 V < Ue 300 V
Test Voltage
700 VDC
(secondary <–> PE)
2300 VDC
(primary <–> PE)
Buffering of power failures: > 20 ms
Complies with the
NAMUR
recommendation NE
21 of August 1998 at a
repeat rate of 1 s
Power input 168 W
Power loss 44 W
Backup current Max. 100 µA at power
off
Backup batteries (optional) 2 x Lithium AA,
3.6 V / 1.9 Ah
Protective separation
to IEC 61131-2 Yes