Analog Modules

5-113

S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
Status, Interrupts, Diagnostics
Interrupts
Hardware interrupt Parameters can be
assigned
Hardware interrupt when
limit has been exceeded Parameters can be
assigned
Diagnostic Interrupt Parameters can be
assigned
Diagnostic functions
Group error display
For internal fault
For external fault
Red LED (INTF)
Red LED (EXTF)
Diagnostic information
readable Yes
Substitute value can be applied No
Data for Selecting a Sensor
Input range (rated values)/Input
resistance
Voltage " 25 mV/1 M
" 50 mV/1 M
" 80 mV/1 M
" 250 mV/1 M
" 500 mV/1 M
" 1 V/1 M
" 2.5 V/1 M
" 5 V/1 M
1 V to 5 V1 M
" 10 V/1 M
Current 0 mA to 20 mA50
" 5 mA/50
" 10 mA/50
" 20 mA/50
4 mA to 20 mA50
Resistors 0 to 48 1 M
0 to 150 1 M
0 to 300 1 M
0 to 600 1 M
0 to 6000 1 M
(can be used up to
5000 )
Thermocouples TC type B/1 M
TC type R/1 M
TC type S/1 M
TC type T/1 M
TC type E/1 M
TC type J/1 M
TC type K/1 M
TC type U/1 M
TC type L/1 M
TC type N/1 M
Resistance thermometer Pt 100/1 M
Pt 200/1 M
Pt 500/1 M
Pt 1000/1 M
Ni 100/1 M
Ni 1000/1 M
Maximum input voltage for
voltage input
(destruction limit)
Max. 18 V continuous;
75 V for 1 ms (cycle
factor 1 : 20)
Maximum input current for
current input (destruction limit) 40 mA
Connection of the signal
sensor
For measuring voltage Possible
For measuring current
As two-wire
transmitter Possible
As four-wire
transmitter Possible
For measuring resistance
With two-conductor
terminal Possible; cable
resistance is also
measured
With three-conductor
terminal Possible
With four-conductor
terminal Possible
Load of the two-wire
transmitter Max. 750
Characteristic linearization Parameters can be
assigned
For thermocouples Types B, R, S, T, E, J,
K, U, L, N
For
resistance thermometer Pt 100, Pt 200, Pt 500,
Pt 1000, Ni 100,
Ni 1000
Temperature compensation Yes, programmable
Internal temperature
compensation No
External temperature
compensation with
compensating box
Possible
External temperature
compensation with Pt 100 Possible
Compensation for
definable reference
junction
temperature
Possible
Unit for temperature
measurement Degrees Celsius