Analog Modules

5-115

S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
Table 5-64 Parameters of the SM 431; AI 16 16 Bit, continued
Parameter ScopeParameter
Type
Default2)
Value Range
Measurement
Measuring type Disabled
U Voltage
4DMU Current
(4-wire transmitter)
2DMU Current
(two-wire transmitter)
R-4L Resistor
(four-conductor terminal)
R-3L Resistor
(three-conductor terminal)
RTD-4L Thermal resistor
(linear, four-conductor
terminal)
RTD-3L Thermal resistor
(linear, three-conductor
terminal)
TC-L Thermocouple (linear)
U
Static Channel
Measuring range Refer to Section 5.22.2 for the
measuring ranges of the input
channels that you can set.
"10 V
teference
Temperature – 273.15 to 327.67 oC0.00 oC
Interference
suppression 400 Hz; 60 Hz; 50 Hz 50 Hz
Smoothing None
Low
Average
High
None
Dynamic Module
Ref. junction None
RTD on Channel 0
Reference temperature value
None
1) If you use the module in ER-1/ER-2, you must set this parameter to “No” because the interrupt lines are
not available in ER-1/ER-2.
2) Only in the CC (central controller) is it possible to start up the analog modules with the default settings.
A Point to Note About Channels for Hardware Interrupts with the End of ScanCycle Trigger

You can parameterize hardware interrupts for the end of scan cycle for one of the

16 channels because the module can only trigger these interrupts on one channel.