Chapter 7 FRU/CRU Replacement Procedures 7-11
7.6.4.2 Sun StorEdge 5310 NAS Fan Module Replacement
Replacing the fan module is essentially the reverse of the procedure described in
“Sun StorEdge 5310 NAS Fan Module Removal” on page7-9.
1. Note the raised tabs on the chassis floor and the corresponding notches in the
bottom of the fan module.
2. Lower the fan module until it is just above the chassis floor.
3. Align the notches in the fan module w ith the raised tabs on the chassis and lower
the fan module onto the floor.
4. While pressing down on the fan module, slide it to the right until the latch snaps
into place.
5. Plug the fan cables into the server board system fan connectors.
6. Make sure the USB cable is routed along the top of the fan module.
7. Connect the flex circuit cable to the backplane.
8. Install the flex circuit cable retention clip.
9. Install the full-height PCI riser board.
10. Replace the plastic processor air duct.
11. Thread the memory fan power cable through the retaining hooks on the plastic
processor air duct.
12. Replace the chassis cover.