11.0 Appendix A

PowerPod-400 Serial Commands

Command

Name

Query

 

Response

 

 

Channel 1 Display

C1

CH1 ddd.dd U of M GasID

 

Channel 2 Display

C2

CH2 ddd.dd U of M GasID

 

Channel 3 Display

C3

CH3 ddd.dd U of M GasID

 

Channel 4 Display

C4

CH4 ddd.dd U of M GasID

 

 

 

CH1 ddd.dd U of M GasID

 

All Channels’ Display

C5

CH2 ddd.dd U of M GasID

 

CH3 ddd.dd U of M GasID

 

 

 

 

 

 

CH4 ddd.dd U of M GasID

SP1<dd.ddd>

Set Point - Channel 1

SP1

SP1 ddd.dd

notes 1, 2

SP2<dd.ddd>

Set Point - Channel 2

SP2

SP2 ddd.dd

 

SP3<dd.ddd >

Set Point - Channel 3

SP3

SP3 ddd.dd

 

SP4<dd.ddd >

Set Point - Channel 4

SP4

SP4 ddd.dd

 

A1H<dd.ddd >

Alarm Set Point, Ch1, High

A1H

A1H ddd.dd

notes 1, 2

A1L<dd.ddd >

Alarm Set Point , Ch1, Low

A1L

A1L ddd.dd

 

A2H<dd.ddd >

Alarm Set Point , Ch2, High

A2H

A2H ddd.dd

 

A2L<dd.ddd >

Alarm Set Point , Ch2, Low

A2L

A2L ddd.dd

 

A3H<dd.ddd >

Alarm Set Point , Ch3, High

A3H

A3H ddd.dd

 

A3L<dd.ddd >

Alarm Set Point , Ch3, Low

A3L

A3L ddd.dd

 

A4H<dd.ddd >

Alarm Set Point , Ch4, High

A4H

A4H ddd.dd

 

A4L<dd.ddd >

Alarm Set Point , Ch4, Low

A4L

A4L ddd.dd

 

HY1<ddd>

Hysteresis, Ch1

HY1

HY1 ddd

 

HY2<ddd>

Hysteresis, Ch2

HY2

HY2 ddd

 

HY3<ddd>

Hysteresis, Ch3

HY3

HY3 ddd

 

HY4<ddd>

Hysteresis, Ch4

HY4

HY4 ddd

 

UM1<dd>

Unit of Meas, Ch1

UM1

UM1 dd

 

UM2<dd>

Unit of Meas, Ch2

UM2

UM2 dd

 

UM3<dd>

Unit of Meas, Ch3

UM3

UM3 dd

 

UM4<dd>

Unit of Meas, Ch4

UM4

UM4 dd

 

GS1<ddd >

Gas ID, CH1

GS1

GS1 ddd

 

GS2<ddd >

Gas ID, CH2

GS2

GS2 ddd

 

GS3<ddd >

Gas ID, CH3

GS3

GS3 ddd

 

GS4<ddd >

Gas ID, CH4

GS4

GS4 ddd

 

IN1<d>

I/O Select, Ch1

IN1

IN1 d

rz - rfs

notes 6, 7

IN2<d>

I/O Select, Ch2

IN2

IN2 d

rz - rfs

 

IN3<d>

I/O Select, Ch3

IN3

IN3 d

rz - rfs

 

IN4<d>

I/O Select, Ch4

IN4

IN4 d

rz - rfs

 

FL1<d>

Filter Setting, Ch1

FL1

FL1 d

 

 

FL2<d>

Filter Setting, Ch2

FL2

FL2 d

 

 

FL3<d>

Filter Setting, Ch3

FL3

FL3 d

 

 

FL4<d>

Filter Setting, Ch4

FL4

FL4 d

 

 

ML1<d.dddd>

Multiplier, CH1

ML 1

ML 1 dddd.d

notes 1, 2

ML2<dd.ddd>

Multiplier , CH2

ML 2

ML 2 ddd.dd

 

ML 3<ddd.dd>

Multiplier , CH3

ML 3

ML 3 dd.ddd

 

ML 4<dddd.d>

Multiplier , CH4

ML 4

ML 4 d.dddd

 

164-122012 PowerPOD 400

Page 30 of 42

Page 30
Image 30
Teledyne powerpod 400 instruction manual Appendix a, PowerPod-400 Serial Commands