All installations and services must be performed by qualified service personnel.

b.The bottom edge of the vent termination elbow must be installed at least 12-inches above the outlet of intake termination elbow.

c.The horizontal distance between the inlet and exhaust terminations should be minimized, when possible, and should never exceed 24- inches.

d.The vent and intake systems should utilize the same numbers of elbows and approximately the same length of straight pipe to reach the outside termination.

Figure 8: Typical Relative Locations of Direct Vent Terminations When

Sidewall Venting

3.Exhaust Vent Terminal Location Clearance Requirements

a.The vent terminal shall be located at least 3-feet above any forced air inlet located within 10-feet. Refer to Figure 9 for a depiction of the minimum required clearances between vent terminations and building features according to the National Fuel Gas Code (NFGC).

b.The vent terminal shall be at least 12-inches below, 12-inches horizontally from, or 12-inches above, any door, window, or gravity air inlet into a building. The bottom of the vent terminal shall be located at least 12-inches above grade.

c.The vent terminal shall not be located:

over public walkways or over an area where wetting of surfaces by condensate, or water vapor, could create a nuisance or hazard,

near soffit vents, crawl space vents, or other areas where condensate or water vapor could create a nuisance, hazard, or cause property damage, and

25

Page 27
Image 27
Thermo Products CMA3-50D36N, CMC1-50DV3N, CMC1-50D36N, CMC1-75D36N, CMA3-75D36N, CMC1-75DV3N service manual Sidewall Venting

FAQ

Who should perform installations and services?

All installations and services must be performed by qualified service personnel.

What are the clearance requirements for the vent terminal?

The vent terminal should be located at least 3-feet above any forced air inlet located within 10-feet, and at least 12-inches below, horizontally from, or above any door, window, or gravity air inlet into a building.

What are the typical relative locations of direct vent terminations?

The bottom edge of the vent termination elbow must be installed at least 12-inches above the outlet of intake termination elbow. The horizontal distance between the inlet and exhaust terminations should be minimized, when possible, and should never exceed 24-inches.