IMPORTANT: The room thermostat should be installed 4 to 5 feet above the floor on an interior wall which is relatively free from direct sources of heat (sunlight or supply airflow) or exposure to cold (drafts from open windows and doors). The nominal anticipator setting is 0.8 amperes, for the CMA/CMC (refer to the thermostat literature for additional information).

Four-conductor thermostat wire is recommended for 24 VAC, low-voltage, control circuit wiring. However, only 2 wires are required for the furnace (a heating application only).

Electrical Wire

Diameter

(AWG)

24

22

20

18

Maximum Recommended

Thermostat Wire Length

(Feet)

55

90

140

225

Once the furnace is installed, check the thermostat anticipator for proper nominal setting.

1.Connect a multimeter, capable of reading milliamps (mA), in series with the low voltage wires to the thermostat.

2.Increase the thermostat setting, or create a “call for heat”.

3.Read the value of the thermostat current, in milliamps.

4.Adjust the heat anticipator of the thermostat to the value read by the multimeter.

If the heat anticipator is set too high, the furnace may delay activation of a heating cycle for too long. If the heat anticipator is set too low, the furnace may cycle too frequently. Either condition may not provide optimal comfort to the homeowner.

32

Page 34
Image 34
Thermo Products CMA3-75D36N, CMC1-50DV3N Electrical Wire Diameter AWG, Maximum Recommended Thermostat Wire Length Feet

FAQ

What is the recommended thermostat wire length?

The recommended thermostat wire length is 55 feet.

How do I adjust the heat anticipator of the thermostat?

To adjust the heat anticipator of the thermostat, connect a multimeter in series with the low voltage wires to the thermostat, increase the thermostat setting, or create a call for heat, then read the value of the thermostat current in milliamps and adjust the heat anticipator to match.

Why is proper thermostat anticipator setting important?

Proper thermostat anticipator setting is important to ensure optimal comfort for the homeowner. If set too high, the furnace may delay activation of a heating cycle for too long. If set too low, the furnace may cycle too frequently.