Thermo Products CMC1-50D36N, CMC1-50DV3N V.Starting The Unit A. Sequence Of Operations

Models: CMC1-75DV3N CMA3-75D36N CMA3-50D36N CMC1-75D36N CMC1-50D36N CMC1-50DV3N

1 65
Download 65 pages 47.5 Kb
Page 43
Image 43
V.STARTING THE UNIT

All installations and services must be performed by qualified service personnel.

V.STARTING THE UNIT

A. SEQUENCE OF OPERATIONS

AT ANY TIME THE

 

 

 

CONTINUOUS SAFE OPERATION CHECK

GAS VALVE IS

 

 

 

IF FLAME SIMULATION CONDITION

NOT ENERGIZED

 

 

PRESENT OR ROLL-OUT SWITCH OPENS, SYSTEM

 

 

 

ENERGIZES INDUCER FAN FOR 15 SECONDS AND CIRCULATOR BLOWER AT

START

 

 

HEATING SPEED UNTIL SITUATION CORRECTION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

THERMOSTAT CALLS FOR

 

 

 

 

 

 

 

HEAT, CONTACTS CLOSE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CONTROL BOARD ENERGIZED,

 

 

 

 

 

INDUCER ENERGIZED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PRESSURE SWITCH SENSES

 

 

ADEQUATE DIFFERENTIAL PRESSURE,

 

 

 

 

 

CONTACTS CLOSE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

POWER IS APPLIED TO

 

POWER INTERRUPTION

THE SILICON NITRIDE

 

SYSTEM SHUTS OFF,

IGNITOR. IGNITOR

 

RESTARTS WHEN POWER

WARM-UP IS 20 SECONDS.

 

IS RESTORED.

START

 

 

 

AFTER IGNITOR WARM-UP,

 

TRIAL

 

THE GAS VALVE IS

 

FOR

 

ENERGIZED TO OPEN

 

IGNITION

 

 

 

 

 

 

 

 

 

FLAME MUST BE DETECTED

 

IF FLAME IS NOT DETECTED, THE

WITHIN 4 SECONDS IF

 

GAS VALVE IS DE-ENERGIZED,

FLAME IS DETECTED, THE

 

THE IGNITOR IS TURNED OFF AND

 

DELAY-TO-FAN-ON TIME

 

THE CONTROL BOARD CONTROL GOES

BEGINS (45 SECONDS)

 

INTO "RETRY" SEQUENCE.

41

Page 43
Image 43
Thermo Products CMC1-50D36N, CMC1-50DV3N, CMC1-75D36N, CMA3-50D36N, CMA3-75D36N V.Starting The Unit A. Sequence Of Operations

FAQ

What personnel should perform installations and services for Thermo Products Furnace?

All installations and services must be performed by qualified service personnel.

What is the warm-up time for the ignitor?

The warm-up time for the ignitor is 20 seconds.

What happens if the flame is not detected within 4 seconds?

If the flame is not detected within 4 seconds, the gas valve is de-energized, and the control board control goes into 'retry' sequence.