All installations and services must be performed by qualified service personnel.
Yes
AFTER GAS VALVE
OPENS, DO THE
BURNERS IGNITE?
Yes
DO BURNERS STAY
LIT PAST PROOF OF FLAME CHECK?
|
|
|
|
|
|
|
|
|
|
|
No |
| CHECK FOR PROPER |
|
| ADJUST TO 3.5" FOR NATURAL GAS | |||||
|
| MANIFOLD PRESSURE. |
|
|
|
| OR 10.0" WC FOR LP GAS | |||
|
|
|
|
|
|
|
|
|
|
|
|
|
| Yes |
|
|
|
|
| ||
|
|
|
|
|
|
|
| |||
|
|
|
|
| No |
|
|
| ||
|
| IS IGNITOR |
|
| REPOSITION TO |
| ||||
| POSITIONED CORRECTLY? |
|
|
|
| CORRECT LOCATION. |
| |||
|
|
|
|
|
|
|
|
|
|
|
|
| Yes |
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
| DOES THE INTEGRATED CONTROL |
|
| CHECK ACROSS THE |
|
| ||||
| ENERGIZE THE | No |
| CIRCULATING AIR | No | REPLACE THE | ||||
| CIRCULATING AIR BLOWER |
|
|
| BLOWER TERMINALS |
|
| |||
|
|
|
|
|
| INTEGRATED CONTROL. | ||||
| AFTER THE 45 SECOND |
|
| "CIR N" & "HEAT" |
| |||||
|
|
|
|
| ||||||
|
| TIME DELAY. |
|
| FOR PROPER VOLTAGE. |
|
|
Yes |
|
|
|
|
|
|
|
| CONFIRM IF |
DOES THE CIRCULATING | No |
|
| EITHER BLOWER WHEEL |
DOES BLOWER | No | IS RUBBING AGAINST | ||
AIR FAN COME ON |
|
| HOUSING OR MOTOR | |
| SPIN FREELY? |
| ||
WHEN ENERGIZED? |
|
| SHAFT IS SPINNING | |
|
|
| ||
|
| Yes |
| FREELY AND REPAIR |
|
|
| OR REPLACE AS NECESSARY. | |
Yes |
|
| Yes |
|
|
| IS CAPACITOR | REPLACE MOTOR | |
|
|
| ||
|
| WORKING PROPERLY |
| |
|
|
|
|
No
REPLACE CAPACITOR
55