Thermo Products CMC1-50D36N, CMC1-50DV3N C.Alcove Installation, Figure D.CLOSET INSTALLATION

Models: CMC1-75DV3N CMA3-75D36N CMA3-50D36N CMC1-75D36N CMC1-50D36N CMC1-50DV3N

1 65
Download 65 pages 47.5 Kb
Page 19
Image 19
C.ALCOVE INSTALLATION

All installations and services must be performed by qualified service personnel.

C.ALCOVE INSTALLATION

In this application, a minimum of 18 inches of clearance must be provided to the front of the unit. See Figure 4.

Note – access to diagnostic view port.

CMA3 SERIES

CMC1 SERIES

Figure 4.

D.CLOSET INSTALLATION

1.The return air opening into the closet is to have a minimum free area of 250 sq. in. (see Figure 5).

2.The return air opening may be located in the top, center or (ideally) bottom of the closet door or side wall.

17

Page 19
Image 19
Thermo Products CMC1-50D36N, CMC1-50DV3N, CMC1-75D36N, CMA3-50D36N C.Alcove Installation, Figure D.CLOSET INSTALLATION

FAQ

Who should perform installations and services for Thermo Products furnaces?

All installations and services must be performed by qualified service personnel.

What is the minimum clearance required for alcove installation?

A minimum of 18 inches clearance must be provided to the front of the unit.

What is the minimum free area required for return air opening in closet installation?

The return air opening into the closet is to have a minimum free area of 250 sq.in.