All installations and services must be performed by qualified service personnel.
gas flame. Should acid compounds form in your furnace, it may reduce the life of the furnace.
H. Direct Venting Through a Sidewall
1. Vent And Combustion Air Pipes
Vent and combustion air pipes may pass through a maximum wall thickness of 18 inches. The minimum wall thickness is 2 inches. Referring to Figure 7, the maximum distance from the outer wall to the center of the elbow is 12 inches.
Figure 7: Proper Direct Vent Terminations (RH & LH views) and Vent
Termination Only w/o Outside Combustion Air Intake (RH view)
NOTICE: If exterior sidewall building materials are subject to degradation from contact with flue gases or moisture, a minimum
2. Exhaust Vent Termination Elbow
The exhaust vent termination elbow shall be installed in accordance with these instructions and any applicable local codes. Refer to Figures 7 and 8 for typical examples of proper terminations.
a. The exhaust vent termination must be installed in the same atmospheric pressure zone (i.e. on the same wall) as the air intake termination.
24