Thermo Products CMC1-75D36N, CMC1-50DV3N Figure K. CONDENSATE DRAIN LINE AND TRAP ASSEMBLY

Models: CMC1-75DV3N CMA3-75D36N CMA3-50D36N CMC1-75D36N CMC1-50D36N CMC1-50DV3N

1 65
Download 65 pages 47.5 Kb
Page 32
Image 32
Figure 13.

All installations and services must be performed by qualified service personnel.

CEILING: Frame out area around where PVC pipe is to penetrate ceiling. Cut a 2-3/8” diameter hole for 2” PVC in the ceiling and a corresponding hole in a firestop to be made of a minimum of 18 gauge galvanized metal large enough to cover the entire framed area. Cut PVC pipe so that it extends up past the fire stop far enough to engage a PVC coupling that will rest on the fire stop and act as a support. Seal between the pipe coupling and fire stop with high temperature RTV silicone sealant (see Figure 13). Continue installing PVC pipe to exhaust vent and combustion air intake termination as described previously.

Figure 13.

K. CONDENSATE DRAIN LINE AND TRAP ASSEMBLY

1. Figure 14 illustrates the typical drain trap connection for a CMA/CMC furnace. (Trap will be installed at factory.) Connect condensate drain trap to building drain system.

2. An optional condensate neutralizer kit (P/n 320095) is available when gas furnace condensate needs to be neutralized (pH increased) prior to discharge into drain system.

3. An optional mini condensate pump (P/N 350224) is available. This pump will fit into the vestibule of the furnace.

Instructions will be included with pump if this option is utilized.

Figure 14.

30

Page 32
Image 32
Thermo Products CMC1-75D36N, CMC1-50DV3N, CMC1-50D36N, CMA3-50D36N Figure K. CONDENSATE DRAIN LINE AND TRAP ASSEMBLY

FAQ

Who should perform installations and services for Thermo Products Furnace?

All installations and services must be performed by qualified service personnel.

What is the recommended diameter for the hole in the ceiling for PVC pipe installation?

A 2-3/8 diameter hole is recommended for 2 PVC in the ceiling.

Is there an optional condensate neutralizer kit available for gas furnace condensate?

Yes, an optional condensate neutralizer kit P/n 320095 is available when gas furnace condensate needs to be neutralized pH increased prior to discharge into drain system.