Thomas & Betts RZ405, RGM 405 Gas Piping and Pressures, Manifold or Orifice Pressure Settings

Models: RZ405 RGM 405

1 24
Download 24 pages 39.73 Kb
Page 13
Image 13
9. Gas Piping and Pressures

9. Gas Piping and Pressures

WARNING: This appliance is equipped for a maximum gas supply pressure of 1/2 pound, 8 ounces, or 14 inches water column. Supply pressure higher than 1/2 pound requires installation of an additional lockup-type service regulator external to the unit.

PRESSURE TESTING SUPPLY PIPING

Test Pressures Above 1/2 PSI: Disconnect the heater and manual valve from the gas supply line which is to be tested. Cap or plug the supply line.

Test Pressures Below 1/2 PSI: Before testing, close the manual valve on the heater.

All piping must be in accordance with requirements outlined in the National Fuel Gas Code ANSI Z223.1a (latest edition) or CAN/CGA- B149.1 and B149.2 (See Paragraph 1). Gas supply piping installation should conform with good practice and with local codes.

Unit heaters are orificed for operation with natural gas having a heating value of 1000 (± 50) BTUH per cubic ft or propane gas with a heating value of 2550 BTUH per cubic ft. If the gas at the installation site does not meet these specifications, consult the factory for proper orificing.

Pipe joint compounds (pipe dope) shall be resistant to the action of liquefied petroleum gas or any other chemical constituents of the gas being supplied.

Install a ground joint union and manual shutoff valve upstream of the unit control system as shown in Figure 13. The 1/8" plugged tapping in the shutoff valve provides connection for a supply line pressure test gauge. The National Fuel Gas Code requires the installation of a trap with a minimum 3" drip leg. Local codes may require a minimum drip leg longer than 3" (typically 6"). Bleed gas lines of trapped air.

Gas connection is either 1/2" or 3/4" depending on size and type of gas.

Size

Gas

Gas Connection

150-200

Natural

1/2"

250-400

Natural

3/4"

150-400

Propane

1/2"

Leak-test all connections by brushing on a leak-detecting solution.

Immediately upstream of the gas

From Gas Supply

supply connection, install a manual

 

shutoff valve with a 1/8” NPT

 

plugged tap accessible for test

 

gauge connection.

 

 

To Controls

 

From

 

 

Gas

Ground Joint Union

Manual

Supply

 

 

Gas Valve

 

 

 

NOTE:

 

6” Drip Leg

Connections

Figure 13 -

shown are by

 

Supply Piping

 

the installer.

 

 

Connection

WARNING: All components of a gas supply system must be leak tested prior to placing equipment in service. NEVER TEST FOR LEAKS WITH AN OPEN FLAME. Failure to comply could result in personal injury, property damage or death.

Manifold or Orifice Pressure Settings

Measuring manifold gas pressure cannot be done until the heater is in operation. It is included in the steps of the "Check-Test-Start" proce- dure in Paragraph 22. The following warnings and instructions apply.

WARNING: Manifold gas pressure must never exceed 3.5" w.c. for natural gas or 10" w.c. for propane gas.

For Natural Gas: Manifold gas pressure is regulated by the combina- tion valve to 3.5" w.c. Inlet pressure to the valve must be a minimum of 5" w.c. or as noted on the rating plate and a maximum of 14" w.c.

For Propane Gas: Manifold gas pressure is regulated by the combina- tion valve to 10" w.c. Inlet pressure to the valve must be a minimum of 11" w.c. and a maximum of 14" w.c.

Before attempting to measure or adjust manifold gas pressure, the inlet

Sizing a Gas Supply Line

Capacity of Piping - Cubic Feet per Hour based on 0.3" w.c. Pressure Drop

Specific Gravity for Natural Gas -- 0.6 (Natural Gas -- 1000 BTU/Cubic Ft)

Specific Gravity for Propane Gas -- 1.6 (Propane Gas -- 2550 BTU/Cubic Ft)

Length

of

Pipe

Diameter of Pipe

1/2"3/4"1"1-1/4"1-1/2"2"

Natural Manifold or Orifice Pressure Settings Propane Natural Sizing a Gas Supply Line Propane Natural Manual background Propane Natural Manual background Propane Natural Manual background Propane Natural Manual background Propane

20’

92

56

 

190

116

350

214

730

445

1100

 

671

2100

1281

30’

73

45

 

152

93

285

174

590

360

890

 

543

1650

1007

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40’

63

38

 

130

79

245

149

500

305

760

 

464

1450

885

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50’

56

34

 

115

70

215

131

440

268

670

 

409

1270

775

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

60’

50

31

 

105

64

195

119

400

244

610

 

372

1105

674

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

70’

46

28

 

96

59

180

110

370

226

560

 

342

1050

641

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

80’

43

26

 

90

55

170

104

350

214

530

 

323

990

604

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

90’

40

24

 

84

51

160

98

320

195

490

 

299

930

567

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100’

38

23

 

79

48

150

92

305

186

460

 

281

870

531

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

125’

34

21

 

72

44

130

79

275

168

410

 

250

780

476

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

150’

31

19

 

64

39

120

73

250

153

380

 

232

710

433

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

175’

28

17

 

59

36

110

67

225

137

350

 

214

650

397

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

200’

26

16

 

55

34

100

61

210

128

320

 

195

610

372

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note: When sizing supply lines, consider possibilities of future expansion and increased requirements.

 

 

 

 

Refer to National Fuel Gas Code for additional information on line sizing.

 

 

 

Mfg No. 164771, Page 13

Page 13
Image 13
Thomas & Betts RZ405, RGM 405 Gas Piping and Pressures, Manifold or Orifice Pressure Settings, Sizing a Gas Supply Line