Thomas & Betts RZ405, RGM 405 dimensions Combustion Air Inlet, Venter Outlet, Concentric Adapter

Models: RZ405 RGM 405

1 24
Download 24 pages 39.73 Kb
Page 5
Image 5
1.Combustion Air Inlet

7A. Venting and Combustion Air Requirements for Separated-Combustion Installation (must use either Option CC2 or CC6)

Specific Requirements (read all before installing)

Comply with the specific requirements and instructions in the following paragraphs and illustrations.

1.Combustion Air Inlet

Diameter is 5" for Sizes 150 and 200 and 6" for Sizes 250, 300, 350, and 400.

Use tin snips or aviation shears to cut out the hole in the top of the heater (See Figure 2). Insert the pipe through the hole and attach it to the collar inside the heater. Seal the joint. (Larger size heaters have oval collars. If the collar is oval, form the pipe to fit the collar.)

2.Venter Outlet

The venter outlet size is 5" for Sizes 150, 200, and 250 and 6" for Sizes 300, 350, and 400. A minimum length of 12" of straight pipe is required at the venter outlet.

3.Concentric Adapter

If installed as a separated-combustion unit, a concentric adapter is required.

Option CC2 and CC6 - The concentric adapter is a metal box that attaches to the inside of the building. See the illustrations and dimenstions in Figures 3A and 3B. Option CC6 is horizontal; Option CC2 is vertical. (Op- tion kits also include a vent terminal and combustion air inlet or guard.)

Figure 2 - Attach Combustion Air Pipe

Venter

Use tin snips

Outlet

 

to cut out

 

hole for

 

combustion

 

air pipe

 

Collar for

 

connecting

 

combustion air

 

pipe

 

1)Remove door panel.

2)Cut out the hole.

3)Slide pipe down through hole.

4)If collar is oval, form pipe to fit. Attach pipe to collar with sheetmetal screws and seal the connection.

Figure 3A - Concentric Adapter Assembly in Options CC2 and CC6

View of Heater Connection Side

Collar for

 

connecting

 

indoor portion

 

of the

 

combustion

 

air pipe

Install rubber seal

 

 

for vent pipe

View of Vent Terminal Connection Side

Collar for outside portion of the combustion air pipe (vent pipe extends through the box internally concentric to the outside portion of the combustion air pipe)

2” (51mm)

6” (152mm)

2” (51mm)

End View

H

Figure 3B - Concentric Adapter Box

Dimensions - inches (mm)

CAUA

150,200

250,300,350,400

A

5 (127)

6 (152)

B

4 (102)

5 (127)

C

4 (102)

4 (102)

D

7-1/2 (191)

7-1/2

E

5 (127)

5 (127)

F

4 (102)

5 (127)

G

16-1/2 (419)

16-1/2 (419)

H

8 (203)

10 (254)

J

6 (152)

8 (203)

J = Diameter of the Collar for attaching the "Outside" Portion of the Combustion Air Pipe

Top View of the Concentric Adapter

Box Showing Air Flow

2.Venter Outlet = Combustion Air Flow

= Exhaust (Vent) Gas Flow

Field-supplied vent pipe passes through the rubber seal on the concentric adapter box, extending out both sides of the box

A = Diameter of the Collar for attaching the inside Combustion Air Pipe from the Heater

F

E

3.Concentric AdapterB

D G

C

Side View - Side of the

Adapter Box that Connects

to the Heater

Mfg No. 164771, Page 5