Thomas & Betts RZ405, RGM 405 dimensions 6B 22 559mm minimum Snow

Models: RZ405 RGM 405

1 24
Download 24 pages 39.73 Kb
Page 9
Image 9
6B
Seal the seam in the vent pipe.

"X" is the length of combustion air pipe required through and above the roof

"X" must equal roof thickness plus clearance required for anticipated snow

plus ridge and/or parapet clearance "X" must not exceed 60" (1524mm)

V Manual backgroundFlowent

6A

Install the vent pipe by inserting it into the terminal side of the box and pushing it out through the seal on the heater side.

NOTE: Be sure flow direction is correct.

2c) Attach the outside portion of the com-

bustion air pipe to the box. Determine the length of the combustion air pipe so that dimension "X" (Figure 6A) is equal to the roof thickness, plus snow depth and ridge or parapet clearance, but does not exceed 60" (1524 mm). Attach the combustion air pipe to the collar with sheetmetal screws being careful not to penetrate the vent pipe.

3. Attach the concentric adapter. Insert

the vent pipe and combustion air pipe up

through the roof and secure the adapter box.

6B

22"

(559mm) minimum

Snow

 

Combustion

 

air pipe

Field-supplied

Flow

mounting brackets

Combustion

 

Flash the combustion air pipe to the outside

of the roof as required.

4. Slide the combustion air inlet over the

Clearance

 

Air

Concentric

 

Adapter Box

 

Collar for combustion

 

air pipe.

 

Vent Pipe - when a taper-type reducer

Install seal

is required in the vent pipe; it must be no

in vent pipe

more than 6” (152mm) from the box.

opening

cause the pipe diameter does not change); plus bracket length; plus the width of the roof; plus the length of the outer inlet air pipe; plus a minimum of 22" (559mm).

Lubricate the seal and pipe with liquid soap or a rubber lubri- cant. (Installation Tip: Spray cooking oil works well as a lubri- cant for this task.) Being sure the pipe is in the proper flow direction, slide the end through the box and push it out through the rubber seal. Push evenly using caution not to displace the seal from its position on the edge of the hole. If the rubber seal moves, slide the pipe back slightly, re-position the seal, and slide the pipe through again.

Position the vent pipe so that it will extend a minimum of 22" (559mm) past the end of the combustion air pipe. See Figure 6B.

A maximum of 6" (152mm) of vent pipe should extend out the heater side. Any time the pipe is re-positioned, re-check the seal to be sure that it has not rolled. Adjust the pipe and seal until the pipe is the correct length on each side of the box and the seal is over the edge of the hole and tight to the entire circumference of the pipe.

6C

1)Slide combustion

vent pipe and fasten the collar

to the end of the combustion air

 

air inlet over the

 

pipe with sheet metal screws

 

vent pipe

 

(See Figure 6C). Seal joint at top

 

2)Fasten to the end

 

between vent pipe and combus-

 

of the combus-

 

tion air inlet with silicone seal-

 

tion air pipe

 

ant to prevent water leakage.

 

3)Seal the top joint

 

5. Attach the exhaust termi-

 

with silicone

 

nal with sheet metal screws (See

 

 

 

 

 

Install field-supplied

Figure 6D).

 

6. Vertical vent terminal/combus-

 

flashing at roof

tion air inlet is installed and ready

 

opening (flashing not

for connection to the heater.

 

illustrated).

 

 

7. Connect Concentric Adapter

 

 

Box to the Heater - Use the pipe speci-

 

Exhaust

 

fied and joints required for type of pipe.

 

Terminal

 

If collars at the heater or adapter are dif-

 

 

 

12" (305mm)

ferent diameters from the pipe (use only

 

diameters allowed on page 6), make con-

 

minimum

 

nection with field-supplied taper-type re-

 

 

 

 

ducer or enlarger.

 

Combustion

A minimum of 12" (305 mm) of

 

straight pipe is required at the venter

 

Air Inlet

outlet. Due to the high temperature, do

 

 

not enclose the vent pipe or place pipe

 

6D

closer than 6" (152 mm) to combustible

 

 

material.

 

Installation of the vertical vent and combustion air system on your sepa- rated-combustion unit is complete. Refer to Figure 6E and verify that all installation requirements are met.

Figure 6E - Installation of Separated-Combustion Unit with Vertical Vent and Combustion Air Pipes (Option CC2)

 

Vent

 

Terminal

Flue

Seal with high

temperature silicone

Exhaust

rubber sealant supplied

(Vent )

with the kit.

Pipe

 

 

Combustion

 

Air Inlet

 

Flashing

 

(field supplied)

 

Roof

Rear

Combustion Air Pipe

 

View

Concentric

 

Vent

Adapter

Pipe

 

Side View

 

12” (305mm)

5 ft (1524mm)

 

maximum (Size

18”(457mm)

according to

minimum

anticipated

snow depth.

 

 

Concentric

 

Adapter

"Through-the-Roof" View of a typical installation of a vertical vent/inlet air terminal and concentric adapter (Option CC2)

9-3/8”

(238mm)

6 ft (1829mm)

minimum

 

Wall or

11” (279mm)

Adjoining

Building

Flashing (field supplied)

Roof

Thimble

Mfg No. 164771, Page 9

Page 9
Image 9
Thomas & Betts RZ405, RGM 405 dimensions 6B 22 559mm minimum Snow