TYPICAL WIRING DIAGRAMS (cont'd)
Figure 18 - Typical Wiring Diagram for Models CAUA with Belt-Drive Blower Motor
|
|
| OPTIONAL DISCONNECT SWITCH | G |
| GRD |
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
| (SEE NOTE) |
|
|
|
|
|
|
|
| INHERENTLY |
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
| MOTOR |
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| PROTECTED |
|
| |||
|
|
|
|
|
|
|
|
|
|
|
| CONTACTOR |
|
|
| BLOWER |
|
| ||
|
|
|
|
|
|
|
|
| L1 | BK |
|
|
| BK |
|
| MOTOR |
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
OR 230/1/60 |
|
|
|
|
|
|
|
|
| W |
|
|
| W |
|
|
|
|
|
|
208 |
|
|
|
|
|
|
|
| L2 |
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| G | GRD |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
| BK |
|
|
|
|
|
|
|
| W |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| DSI CONTROL |
|
| VENTER MOTOR |
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
| (SEE NOTE #8) |
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
L1 | BK |
|
|
|
|
|
|
|
| BK |
| LINE | CMB |
| BK OR BR |
| BK OR BL |
| L2 | |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
| VAC HOT | BLWR AUX |
|
|
|
| MOTOR |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| CONTACTOR COIL |
| |
|
| 1 | BL |
|
|
|
|
|
| BL |
| 24VAC | ACB HEAT | BK |
|
|
|
| W | L2 |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
|
|
|
|
| FLAME |
|
|
|
|
|
| HOT |
|
|
|
|
|
|
|
|
|
|
|
| ROLLOUT SWITCH |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
| 1 | BL | BL |
|
| CUSTOMER'S |
| BL |
| ROLLOUT | ACB COOL | BK |
|
|
|
|
| L2 | |
|
|
|
|
|
|
|
|
|
| IN |
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
| COOL RELAY COIL |
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
| C | GROUND | BR |
|
|
| BR | 7 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| IGNITOR |
|
|
|
|
| |
|
|
|
|
|
|
| THERMOSTAT |
|
|
|
| HV LEAD |
|
|
|
| BR | 7 |
| |
|
|
|
|
|
|
|
|
|
|
|
| BURNER GROUND |
| |||||||
|
|
|
|
|
|
| TERMINAL STRIP |
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
| R | BL |
|
|
| FLAME SENSE | R |
|
| FLAME SENSING |
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| PROBE |
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
| C |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Y |
|
| PRESSURE SWITCH |
| HIGH |
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
| NC |
|
| LIMIT |
|
| |
|
|
|
| SUBBASEQ539ATHERMOSTATT87F AMPS0.6ATANTICIPATORSET |
|
| R |
| R |
|
|
| Y |
|
|
|
| |||
|
|
|
|
| Y1 |
|
|
| PSW | BK | PILOT | HONEYWELL |
|
| ||||||
|
|
|
|
| R |
|
|
|
|
|
| NO | Y 2 | R | R |
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
| C |
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
| W |
|
|
|
|
|
|
|
|
|
|
|
|
|
| Y |
| Y2 |
|
| BK |
|
| HI LIMIT | Y |
| 2 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| IN |
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
| G |
|
|
|
|
|
|
|
|
|
|
|
|
|
| W |
| W1 | BK |
| Y |
|
| HI LIMIT | R |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| OUT |
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
| LED |
|
|
|
|
|
|
| |
|
|
|
|
| G |
| W2 |
|
| BL | R |
|
|
| TR OR |
| BR | 7 |
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| Y |
|
|
|
|
| BL |
| MAIN |
|
|
|
|
|
|
|
|
|
|
| G |
|
|
|
| VALVE |
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| TH OR |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| CHASSIS GRND. |
|
| MV |
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
| DOOR SWITCH |
|
|
|
|
|
|
|
|
|
| OR PV |
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
| 1 |
| BL | BL | 3 | BL |
| 24V |
| BR |
|
|
|
|
|
| BR | 7 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
| 40 VA. CONTROL |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| BK |
|
|
| Y | TRANSFORMER |
|
|
|
|
|
| Y |
|
L1 |
|
|
|
|
|
| LINE VOLT |
|
|
|
|
|
|
| L2 | |||||
|
|
|
|
|
|
|
|
|
| R |
|
|
|
|
|
|
|
|
|
|
MAIN TERMINAL BLOCK
UNIT TERMINAL STRIP
THERMOSTAT TERMINAL STRIP
WIRING CODE
BLACK - BK
BROWN - BR
RED - R
ORANGE - O
YELLOW - Y
GREEN - G
BLUE - BL
PURPLE - PR
WHITE - W
FACTORY WIRING
FIELD WIRING
OPTIONAL FACTORY
WIRING
| BR | C | ALTERNATE W.R. ORROBERTSHAW |
|
| ||
| BL | MAIN | |
| M | ||
|
| ||
BK |
| PILOT | |
| P | ||
|
|
OPERATING SEQUENCE
1.SET THERMOSTAT SYSTEM SWITCH AT "OFF" POSITION; FAN SWITCH AT "AUTO" POSITION.
2.TURN ON MANUAL GAS VALVE.
3.TURN ON POWER TO UNIT.
4.SET THERMOSTAT SYSTEM SWITCH AT "HEAT" POSITION; FAN SWITCH AT "AUTO" POSITION.
5.THERMOSTAT CALLS FOR HEAT, ENERGIZING THE VENTER MOTOR.
6.VENTER PRESSURE SWITCH CLOSES, FIRING UNIT.
7.BURNER FLAME IS SENSED, AND IN 30 SECONDS THE BLOWER MOTOR IS ENERGIZED.
8.IF THE FLAME IS EXTINGUISHED DURING MAIN BURNER OPERATION, THE INTEGRATED CONTROL SYSTEM CLOSES THE MAIN VALVE AND MUST BE RESET BY INTERRUPTING POWER TO THE CONTROL CIRCUIT (SEE LIGHTING INSTRUCTIONS).
9.SET THERMOSTAT SYSTEM SWITCH AT "COOL" POSITION, FAN SWITCH AT "AUTO" POSITION.
(A)ON A CALL FOR COOLING, BLOWER MOTOR IS ENERGIZED AND COOLING CIRCUIT IS ENERGIZED.
10.WHEN BLOWER DOOR IS OPENED, THE UNIT IS SHUTDOWN.
11.SET THERMOSTAT SYSTEM SWITCH AT "OFF" POSITION, FAN SWITCH AT "AUTO" POSITION, FOR SHUTDOWN.
NOTES
1.THE FOLLOWING CONTROLS ARE FIELD INSTALLED OPTIONS: THERMOSTAT
2.DOTTED WIRING AND COOL RELAY COIL INSTALLED BY OTHERS.
3.CAUTION: IF ANY OF THE ORIGINAL WIRING AS SUPPLIED WITH THE
APPLIANCE MUST BE REPLACED, IT MUST BE REPLACED WITH WIRING MATERIAL HAVING A TEMPERATURE RATING OF AT LEAST 105° C. EXCEPT FOR SENSOR LEAD WIRE WHICH MUST BE 150° C.
4.USE 18 GA. WIRE FOR CONTROL WIRING ON THE UNIT.
5.USE 14 GA. WIRE FOR LINE AND MOTOR WIRING ON UNIT.
6.LINE AND FAN MOTOR BRANCH WIRE SIZES SHOULD BE OF A SIZE TO PREVENT VOLTAGE DROPS BEYOND 5% OF SUPPLY LINE VOLTAGE.
7.ON 208/230V. UNITS THE CONTROL TRANSFORMER HAS A DUAL VOLTAGE PRIMARY. FOR 230V. UNITS, USE BLACK AND YELLOW LEADS (CAP RED).
FOR 208V. UNITS, USE BLACK AND RED LEADS (CAP YELLOW).
8.VENTER MOTOR ON
9.WHEN PROVIDING OR REPLACING FUSES IN THE FUSIBLE DISCONNECT SWITCH USE DUAL ELEMENTS TIME DELAY FUSES AND SIZE ACCORDING TO 1.25 TIMES THE MAXIMUM TOTAL INPUT AMPS.
LED CODES
SLOW FLASH NORMAL OPERATION - NO CALL FOR HEAT FAST FLASH NORMAL OPERATION - CALL FOR HEAT
2 FLASHES SYSTEM LOCKOUT - FAILED TO DETECT OR SUSTAIN FLAME 3 FLASHES PRESSURE SWITCH OPEN OR CLOSED
4 FLASHES HIGH LIMIT OPEN
5 FLASHES FLAME SENSED AND GAS VALVE NOT ENERGIZED
STEADY ON INTERNAL FAILURE
|
| FIELD CONTROL WIRING |
|
| |
TOTAL WIRE |
| DISTANCE FROM | MIN. RECOMMENDED | ||
LENGTH |
| UNIT TO CONTROL |
|
| WIRE GUAGE |
150' | 75' |
|
| #18 GA. WIRE | |
250' | 125' |
|
| #16 GA. WIRE | |
350' | 175' |
|
| #14 GA. WIRE |
Form 405, Page 18