OPTIONAL ACCESSORIES
17. Optional Cased Cooling Coil, Model ACUA, ACUB, or ACUC
This cased cooling coil is designed for use with the Model CAUA upflow heater. It is shipped separately for field installation over the discharge opening of the heater. Before installing, verify that the coil cabinet is the same size as the heater cabinet.
Follow the installation instructions shipped with the cooling coil (Installation Form RZ
Model |
| ACUA |
|
| ACUB |
|
| ACUC |
| |||
S i z e | 060 |
| 072 | 090 | 090 |
| 120 | 150 | 120 | 150 |
| 180 |
Nominal Cooling Capacity (MBH) | 60 |
| 7 2 | 9 0 | 9 0 |
| 120 | 150 | 120 | 150 |
| 180 |
Refrigerant Type | ||||||||||||
Thermal Expansion Valves* | 1 |
| 1 | 1 | 1 |
| 2 | 2 | 2 | 2 |
| 2 |
Approximate Weight (lbs) | 8 3 |
| 8 6 | 105 | 110 |
| 122 | 140 | 176 | 180 |
| 188 |
No. of Intertwining Circuits | 8 |
| 8 | 1 2 | 1 2 |
| 1 2 | 1 8 | 1 2 | 1 6 |
| 1 8 |
Face Area (sq ft) | 7.79 | 7.79 | 9.38 | 14.04 | 11.67 | 13.70 | 17.13 | 15.38 | 17.13 | |||
| ||||||||||||
Airflow (cfm) Low |
| 1800 |
|
| 3000 |
|
| 4000 |
|
| ||
Nominal |
| 2400 |
|
| 4000 |
|
| 5000 |
|
| ||
High |
| 3000** |
|
| 5000** |
|
| 6000** |
|
* - TXV's are factory supplied. Models with two TXV's have intertwined circuiting.
** - Airflow in excess of maximum values shown may result in
Heater/Coil Cross-Reference
Table by Cabinet Size
Heater Model CAUA
150 |
| 200 | 250 | 300 | 350 | 400 |
|
|
|
|
|
|
|
ACUA | ACUB | ACUC | ||||
060 |
| 090 |
|
| 120 | |
072 |
| 120 |
|
| 150 | |
090 |
| 150 |
|
| 180 | |
|
|
|
Figure 19 - A Model ACU cooling coil installed on a Model CAUA heater and the line connection sizes
Suction Line |
| |
Connection(s) | ModelACU | |
Liquid Line | ||
Cased | ||
Connection(s) | Cooling Coil | |
3/4" Drain Line |
| |
Connection |
| |
ModelCAUA |
| |
Heater |
|
Hole for Burner Condensate Drain Tube (use this hole or the one on the opposite side) - see Paragraph 10, page 14
Model | S i z e | Connections |
ACUA 060/072 | (1) 7/8" Suction Line | |
|
|
|
| 060 | (1) 3/8" Liquid Line |
|
|
|
| 072 | (1) 1/2" Liquid Line |
|
|
|
| 090 | (2) 7/8" Suction Lines |
|
|
|
| 090 | (2) 3/8" Liquid Lines |
|
|
|
ACUB | 090/120/150 | (2) 7/8" Suction Lines |
| 090/120 | (2) 3/8" Liquid Lines |
|
|
|
| 150 | (2) 1/2" Liquid Lines |
|
| |
ACUC 120/150/180 | (2) 7/8" Suction Lines | |
|
|
|
| 120 | (2) 3/8" Liquid Lines |
|
|
|
| 150/180 | (2) 1/2" Liquid Lines |
|
|
|
Drain line connection is 3/4" for all sizes.
Burner Condensate Drain
When a system includes a cooling coil, a burner condensate drain must be installed. The parts required for the drain are shipped with the heater. Instructions for installing the drain are in Paragraph 10, page 14.
Electrical Connections
Figure 20 - Typical
Heater Terminal Strip
Low Voltage Wiring (field-supplied)
Thermostat | 24V Supply * |
|
|
|
| ||
Connections |
|
| |
|
|
| |
(Read thermostat |
|
|
|
manufacturer’s | Common |
|
|
installation |
|
| |
|
|
| |
instructions |
|
|
|
before wiring.) | 1st Stage Cooling |
|
|
|
|
| |
|
|
|
|
| 2nd Stage Cooling |
|
|
|
|
|
|
| 1st Stage Heating |
|
|
|
|
|
|
| Optional |
|
|
|
|
|
|
| Fan |
|
|
|
|
|
|
|
|
|
|
R
C
Y1
Y2
W1
W2
G
Condensing Unit Connections (Read
Common manufacturer’s installation instructions before wiring.)
1st stage cooling 24V control relay
2nd stage cooling 24V control relay for Sizes 090, 120, 150, and 180
* A separate 24V control transformer may |
| Legend |
| |
be required for the condensing equipment controls |
|
| ||
|
|
|
| |
Install a jumper wire between RH and RC terminals |
|
| Thermostat wiring - 24V |
|
on the thermostat for single transformer operation. |
|
|
| |
|
| Field control wiring - 24V |
| |
Consult the thermostat manufacturer’s instructions. |
|
|
| |
|
|
|
| |
|
|
|
| |
|
|
|
| |
|
|
| Mfg No. 164771, Page 19 |