OPTIONAL ACCESSORIES

17. Optional Cased Cooling Coil, Model ACUA, ACUB, or ACUC

This cased cooling coil is designed for use with the Model CAUA upflow heater. It is shipped separately for field installation over the discharge opening of the heater. Before installing, verify that the coil cabinet is the same size as the heater cabinet.

Follow the installation instructions shipped with the cooling coil (Installation Form RZ 405-CC), the wiring diagram, and the instructions provided by the compressor manufacturer.

Model

 

ACUA

 

 

ACUB

 

 

ACUC

 

S i z e

060

 

072

090

090

 

120

150

120

150

 

180

Nominal Cooling Capacity (MBH)

60

 

7 2

9 0

9 0

 

120

150

120

150

 

180

Refrigerant Type

R-22

R-22

R-22

R-22

R-22

R-22

R-22

R-22

R-22

Thermal Expansion Valves*

1

 

1

1

1

 

2

2

2

2

 

2

Approximate Weight (lbs)

8 3

 

8 6

105

110

 

122

140

176

180

 

188

No. of Intertwining Circuits

8

 

8

1 2

1 2

 

1 2

1 8

1 2

1 6

 

1 8

Face Area (sq ft)

7.79

7.79

9.38

14.04

11.67

13.70

17.13

15.38

17.13

Rows-Fins/Inch

2-10

2-12

3-10

2-12

3-10

3-12

2-12

3-10

 

3-10

Airflow (cfm) Low

 

1800

 

 

3000

 

 

4000

 

 

Nominal

 

2400

 

 

4000

 

 

5000

 

 

High

 

3000**

 

 

5000**

 

 

6000**

 

* - TXV's are factory supplied. Models with two TXV's have intertwined circuiting.

** - Airflow in excess of maximum values shown may result in blow-off of condensation.

Heater/Coil Cross-Reference

Table by Cabinet Size

Heater Model CAUA

150

 

200

250

300

350

400

 

 

 

 

 

 

 

ACUA

ACUB

ACUC

060

 

090

 

 

120

072

 

120

 

 

150

090

 

150

 

 

180

 

 

 

Figure 19 - A Model ACU cooling coil installed on a Model CAUA heater and the line connection sizes

Suction Line

 

Connection(s)

ModelACU

Liquid Line

Cased

Connection(s)

Cooling Coil

3/4" Drain Line

 

Connection

 

ModelCAUA

 

Heater

 

Hole for Burner Condensate Drain Tube (use this hole or the one on the opposite side) - see Paragraph 10, page 14

Model

S i z e

Connections

ACUA 060/072

(1) 7/8" Suction Line

 

 

 

 

060

(1) 3/8" Liquid Line

 

 

 

 

072

(1) 1/2" Liquid Line

 

 

 

 

090

(2) 7/8" Suction Lines

 

 

 

 

090

(2) 3/8" Liquid Lines

 

 

 

ACUB

090/120/150

(2) 7/8" Suction Lines

 

090/120

(2) 3/8" Liquid Lines

 

 

 

 

150

(2) 1/2" Liquid Lines

 

 

ACUC 120/150/180

(2) 7/8" Suction Lines

 

 

 

 

120

(2) 3/8" Liquid Lines

 

 

 

 

150/180

(2) 1/2" Liquid Lines

 

 

 

Drain line connection is 3/4" for all sizes.

Burner Condensate Drain

When a system includes a cooling coil, a burner condensate drain must be installed. The parts required for the drain are shipped with the heater. Instructions for installing the drain are in Paragraph 10, page 14.

Electrical Connections

Figure 20 - Typical

Heater Terminal Strip

Low Voltage Wiring (field-supplied)

Thermostat

24V Supply *

 

 

 

 

Connections

 

 

 

 

 

(Read thermostat

 

 

 

manufacturer’s

Common

 

 

installation

 

 

 

 

 

instructions

 

 

 

before wiring.)

1st Stage Cooling

 

 

 

 

 

 

 

 

 

 

2nd Stage Cooling

 

 

 

 

 

 

 

1st Stage Heating

 

 

 

 

 

 

 

Optional 2-Stage Heating

 

 

 

 

 

 

 

Fan

 

 

 

 

 

 

 

 

 

 

R

C

Y1

Y2

W1

W2

G

Condensing Unit Connections (Read

Common manufacturer’s installation instructions before wiring.)

1st stage cooling 24V control relay

2nd stage cooling 24V control relay for Sizes 090, 120, 150, and 180

* A separate 24V control transformer may

 

Legend (field-supplied 24V wiring)

 

be required for the condensing equipment controls

 

 

 

 

 

 

Install a jumper wire between RH and RC terminals

 

 

Thermostat wiring - 24V

 

on the thermostat for single transformer operation.

 

 

 

 

 

Field control wiring - 24V

 

Consult the thermostat manufacturer’s instructions.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Mfg No. 164771, Page 19

Page 19
Image 19
Thomas & Betts RZ405, RGM 405 dimensions Optional Cased Cooling Coil, Model ACUA, ACUB, or Acuc, Burner Condensate Drain