OPTIONAL ACCESSORIES (cont'd)
18. Optional Filter Cabinet (return air only)
A filter cabinet designed for 2" pleated disposable or permanent metal filters is shipped separately for field assembly and installation. Depending on the option selected, filters are either shipped with the cabinet or are
To adapt to a variety of applications, the heater cabinet is designed so that the filter cabinet can attach on either the right side, the left side, or the rear of the heater. The larger filter cabinets (left two tables below) are uniquely designed so that the same cabinet can be
All of the filter cabinets have a duct flange for attaching the inlet air duct. For inlet duct dimensions, see Paragraph 8.
Follow the
Figure 21 - Filter Cabinets with Filter Arrangements and Filter Sizes
Option CW4 with 2" Pleated Filters | Option CW7 with 2" Pleated Filters | |
Option CW5 with 2" Permanent Filters | Option CW12 with 2" Permanent Filters | |
Option CW6 for | Option CW11 for | |
• Attaches on Either Side of the Heater | • Attaches on the Rear of the Heater | |
• Vertical (Top) or Horizontal Inlet Opening | • Vertical (Top) or Horizontal Inlet | |
• "V" Filter Rack Arrangement | Opening | |
| • "V" Filter Rack Arrangement | |
Figure 21A - | Figure 21B - | |
Assembled | ||
Assembled with | ||
with | ||
Vertical Air | ||
Inlet Opening | Horizontal | |
Air Inlet | ||
| ||
| Opening |
Option CW8 with 2" Pleated Filters
Option CW9 with 2" Permanent Filters
Option CW10 for
•Attaches on either Side or the Rear of a Size 150 or 200 Heater
•Horizontal Inlet Opening
•"V" Filter Rack Arrangement
Figure 21C -
Small Filter Cabinet for Sizes 150 and 200 only
Sizes of Permanent or Pleated 2"
Filters for Options CW4, CW5, or CW6
Size | CFM | FPM | Filters |
150 | 1800 | 281 | (4) 16 x 16 |
|
|
|
|
| 2400 | 375 | (4) 16 x 16 |
|
|
|
|
| 3000 | 469 | (4) 16 x 16 |
200 | 2400 | 375 | (4) 16 x 16 |
| 3000 | 469 | (4) 16 x 16 |
250 | 3000 | 469 | (4) 16 x 16 |
|
|
|
|
| *4000 | 625 | (4) 16 x 16 |
|
|
|
|
| **5000 | 781 | (4) 16 x 16 |
|
|
| (4) 16 x 16 |
300 | 3000 | 469 | (4) 16 x 16 |
|
|
|
|
| *4000 | 625 | (4) 16 x 16 |
|
|
|
|
| **5000 | 781 | (4) 16 x 16 |
|
|
| (4) 16 x 16 |
350 | 4300 | 448 | (6) 16 x 16 |
| 5000 | 521 | (6) 16 x 16 |
|
|
|
|
| *6000 | 625 | (6) 16 x 16 |
400 | 4300 | 448 | (6) 16 x 16 |
| 5000 | 521 | (6) 16 x 16 |
|
|
|
|
| *6000 | 625 | (6) 16 x 16 |
Sizes of Permanent or Pleated 2" Filters for Options CW7, CW12, or CW11
Size | CFM | FPM | Filters |
150 | 1800 | 281 | (4) 16 x 16 |
|
|
|
|
| 2400 | 375 | (4) 16 x 16 |
|
|
|
|
| 3000 | 469 | (4) 16 x 16 |
200 | 2400 | 375 | (4) 16 x 16 |
| 3000 | 469 | (4) 16 x 16 |
250 | 3000 | 313 | (6) 16 x 16 |
|
|
|
|
| 4000 | 417 | (6) 16 x 16 |
|
|
|
|
| 5000 | 521 | (6) 16 x 16 |
300 | 3000 | 313 | (6) 16 x 16 |
| 4000 | 417 | (6) 16 x 16 |
|
|
|
|
| 5000 | 521 | (6) 16 x 16 |
350 | 4300 | 448 | (6) 16 x 16 |
| 5000 | 521 | (6) 16 x 16 |
|
|
|
|
| *6000 | 625 | (6) 16 x 16 |
400 | 4300 | 448 | (6) 16 x 16 |
|
|
|
|
| 5000 | 521 | (6) 16 x 16 |
|
|
|
|
| *6000 | 625 | (6) 16 x 16 |
Filters for Options CW8, CW9, CW10
Size CFM FPM | 2" Filters | |||
|
|
| Pleated | Permanent |
150 | 1800 | 375 | (2) 12 x 32 | (4) 12 x 16 |
| 2400 | 500 | (2) 12 x 32 | (4) 12 x 16 |
|
|
|
|
|
| *3000 | 625 | (4) 12 x 16 | |
200 | 2400 | 500 | (2) 12 x 32 | (4) 12 x 16 |
|
|
|
|
|
| *3000 | 625 | (4) 12 x 16 |
NOTES:
*Requires 2" permanent filters.
**If using side inlets, two cabinets must be installed, one on each side.
19. Mixing Cabinet (Outside and Return Air)
The optional mixing box for the Reznor® Model CAUA heater is designed to provide the system with a supply air mixture of return air and outside air. Any percentage of outside air can be supplied to the unit as long as the air temperature entering the blower is 35°F or above. The mixing box is available in an assortment of configurations with a selection of actuators and controls. All mixing boxes are completely assembled at the factory for field attachment to the rear of a Model CAUA heater.
Follow the instructions packed with the mixing box to cut out the opening and attach the mixing box. If the mixing box has dampers, follow the
instructions for routing the damper motor wires, and connect the wires according to the wiring diagram. If there are both return air and outside air dampers, follow the directions to adjust the damper linkage.
All mixing box inlet air openings have duct flanges for attachment of ductwork. Ductwork must be attached to the outside air opening. Removable door panels provide for filter access from either end of the cabinet. If the box was ordered with optional filters, it is shipped with the filters installed.
Form 405, Page 20