UPS Specifications
Standard Models: 3.6kVA-RoHS; 3.6kVA; 6kVA; 8kVA
Unit (Capacity) | 3.6 |
| 3.6 kVA (3.1 kW)1 | 6 kVA (5.1 kW)1 | 8 kVA (6.8 kW)1 | ||
(3.1 kW)1 |
|
| |||||
|
|
|
|
|
|
| |
General |
|
|
|
|
|
|
|
Topology |
|
|
| True |
| ||
Certifications |
|
|
| UL, CUL, ISO 9001, |
| ||
Input Characteristics |
|
|
|
|
|
|
|
Input Voltage |
|
|
| ||||
Input Frequency |
|
|
| 45 – 65 Hz |
| ||
Input Capacity |
| 3.6 kVA |
| 6.0 kVA | 8.0 kVA | ||
Input Power Factor |
|
|
| > 0.95 for all loads |
| ||
Current THD (linear load) |
|
|
| < 5% total harmonic distortion |
| ||
Included AC Input Breaker |
| 30 A/277 V |
| 50 A/277 V | 60 A/277 V | ||
Rating |
|
| |||||
|
|
|
|
|
|
| |
Battery Characteristics |
|
|
|
|
|
|
|
Battery Type |
|
| Valve Regulated Lead Acid, Flame Retardant |
| |||
Backup time, fully charged | 8 min. |
|
| 14 min. |
| 7 min. | |
@ 0.7 power factor, 77 °F | minimum2 |
|
| minimum2 |
| minimum2 | |
Backup time, fully charged | 7 min. |
|
| 10 min. |
| 7 min. | |
@ 0.85 power factor, 77 °F | minimum2 |
|
| minimum2 |
| minimum2 | |
Recharge Time |
| 24 hr. (full), 12 hr. (90%) for internal batteries only3 | |||||
Battery Voltage (Nominal) | 144 Vdc |
|
| 216 Vdc |
| 216 Vdc | 288 Vdc |
Output Characteristics |
|
|
|
|
|
|
|
Output Voltage |
|
|
|
| |||
Output Voltage Regulation |
|
| ± 3% |
|
| ||
Output Frequency | ±0.5 Hz/1 Hz/1.5 Hz (factory or authorized service center selectable only) | ||||||
AUTO/MAN Frequency | Factory or authorized service center selectable only | ||||||
Voltage THD |
|
| < 3% for linear load; < 6% for |
| |||
|
|
| < 0.5 Vrms |
| |||
Rated Load Power Factor |
|
|
| 0.85 (0.6 – 1.0) lagging |
| ||
Efficiency |
|
|
| > than 83% (without battery charge) |
| ||
Voltage Transient |
|
|
| < ±8% (Load of 0 – 100 %) |
| ||
Rated Output Current (rms) |
|
| 15 A |
| 25 A | 33.3 A | |
Max. Peak Output Current |
|
| 45 A |
| 75 A | 100 A | |
Inverter Overload Capacity |
|
|
| 125% for 30 sec./150% for 10 sec. |
| ||
Bypass Overload Capacity |
|
|
| 125% for 10 min./1000% for 1 cycle |
| ||
Crest Factor |
|
| 3.0 |
|
|
1.Input/output figures rated for 240 volts. Output ratings given for 0.85PF are only valid when the input voltage is greater than 204 volts; otherwise, ratings given for 0.70PF are applicable.
2.Battery backup time may vary depending on the operating conditions and ambient temperature at the installation site.
3.An initial charge time of 24 hrs. is necessary to obtain proper battery performance level before unit is placed in operation.
1600EP Series Instruction Manual | 15 |