The following screens show the procedure for setting the data variables. They are accessed from the main Data Setting screens (see page 33) when the Shift/Select key is pressed:

Cont’d from Key Lock data setting screen page 33

Cont’d from Buzzer data setting screen page 33

Cont’d from LCD Display Time data setting screen page 33

Cont’d from Auto Run data setting screen page 33

DEFAULT SETTINGS

PUSH: SELECT

DEFAULT SETTINGS

PUSH: SELECT

Loops through both

possibilities

BUZZER VOLUME: 2

TO ACCEPT: SET

BUZZER VOLUME: 0

TO ACCEPT: SET

BUZZER VOLUME: 1

TO ACCEPT: SET

Loops through three

possibilities

LCD SLEEP: 3 MIN TO ACCEPT: SET

LCD SLEEP: 30 MIN

TO ACCEPT: SET

Loops through both

possibilities

AUTO RUN: YES

TO ACCEPT: SET

AUTO RUN: NO TO ACCEPT: SET

Loops through both

possibilities

Shift

Select

Shift

Select

Shift

Select

Shift

Select

Shift

Select

Shift

Select

Shift

Select

Shift

Select

Shift

Select

+MonitorSet

+MonitorSet

+MonitorSet

+MonitorSet

+MonitorSet

+MonitorSet

+MonitorSet

+MonitorSet

+MonitorSet

KEY LOCK: DIS

TO CHANGE: SELECT

KEY LOCK: EN

TO CHANGE: SELECT

Returns to Data Setting screens

(with new value applied)

BUZZER VOLUME: 2 TO CHANGE: SELECT

BUZZER VOLUME: 0 TO CHANGE: SELECT

BUZZER VOLUME: 1 TO CHANGE: SELECT

Returns to Data Setting screens

(with new value applied)

LCD SLEEP: 3 MIN

TO CHANGE: SELECT

LCD SLEEP: 30 MIN

TO CHANGE: SELECT

Returns to Data Setting screens

(with new value applied)

AUTO RUN: YES

TO CHANGE: SELECT

AUTO RUN: NO

TO CHANGE: SELECT

Returns to Data Setting screens

(with new value applied)

Key Lock function: Allows the operator to disable the RUN + STOP button functions. When this function is set to EN the unit will remain in the operating mode it was in when enabled and will not be able to be changed with the RUN + STOP buttons until this function is disabled. With this function set to DIS, the RUN + STOP buttons function normally.

Default setting is DIS.

Buzzer:

2 = High

1 = Low

0 = Off

Default setting is 2 = High (loudest)

LCD Sleep: Displays the number of minutes (3 or 30) of idle time before the LCD will go blank (this is to prolong LCD life). The LCD will be active again once a display button is pressed.

Default setting is 3 MIN.

Auto Run: If set to YES, the unit will automatically start up in the UPS mode (on line) when input voltage is applied, regardless of what mode it was in when shut down.

Default setting is NO.