Operating the UPS

Operating the UPS

Battery Backup Time and Discharge Process

The UPS batteries provide about 5-7 minutes of back-up time depending on the 1600EP unit kVA rating. These times are valid when the unit is operating under full load and at the rated power factor. The exact length of these times will depend on the UPS model used, condition of the batteries, amount and type of load, temperature and other variables. See battery backup time in ‘Standard Specifications’ beginning on pages 15-20.

The following illustration graphically shows the battery discharge process at full load conditions.

Current voltage

imax

imin

vnom

 

 

vlow

 

shutdown

 

 

vmin

 

 

100%

20%

0%

 

battery capacity

 

Battery Low Voltage Tolerances

Excessive discharge will cause the UPS battery voltage to drop. The chart shown below lists the voltage level at which each UPS low-voltage alarm will sound and at what level the low-voltage condition will cause the unit to automatically shut down.

UPS Capacity

3.6 kVA-

3.6 kVA

6 kVA

8 kVA

10 kVA

14 kVA

18 kVA

22 kVA

 

RoHS

 

 

 

 

 

 

 

Nominal voltage (Vnom)

144 Vdc

216 Vdc

216 Vdc

288 Vdc

288 Vdc

288 Vdc

288 Vdc

288 Vdc

Alarm voltage (Vlow)

130 Vdc

192 Vdc

192 Vdc

246 Vdc

246 Vdc

246 Vdc

246 Vdc

246 Vdc

Shutdown voltage (Vmin)

114 Vdc

170 Vdc

170 Vdc

227 Vdc

227 Vdc

227 Vdc

227 Vdc

227 Vdc

1600EP Series Instruction Manual

21

Page 29
Image 29
Toshiba 1600EP Series Operating the UPS, Battery Backup Time and Discharge Process, Battery Low Voltage Tolerances, 100%