Standard Models: 10kVA; 14kVA; 18kVA; 22kVA (cont’d)
Capacity | 10 kVA (8.5 kW)1 |
| 14 kVA (11.9 kW)1 | 18 kVA (15.3 kW)1 |
| 22 kVA (18.7 kW)1 | |
Environment |
|
|
|
|
|
| |
Operating temperature |
|
| 60 Hz (0 – 40 °C) ; 50Hz (0 – 33 °C) |
| |||
(15 – 25° C recommended) |
|
|
| ||||
|
|
|
|
|
| ||
Storage Temperature |
|
|
| ||||
Installation Area | To be installed in a well ventilated area free of airborne dust, | ||||||
metal particles or flammable gas, allow at least 4 inches on all sides | |||||||
| |||||||
Operating Humidity |
|
| 30 – 90% (no condensation) |
| |||
Altitude |
|
| < 3200 ft. (1000 m) above sea level 2 |
| |||
Acoustical Noise | 50 dB (A) maximum @ 1 meter from front panel | ||||||
Heat Generation | 4352 BTU/Hr |
| 6092 BTU/Hr | 7832 BTU/Hr |
| 9600 BTU/Hr | |
Operation Diagnosis |
|
|
|
|
|
| |
Battery Check | Performed on start up, by schedule, | ||||||
Input OV Protection |
|
| Standard |
| |||
Battery Lifetime | UPS calculates battery replacement time based upon | ||||||
battery ambient temperature (LCD display, LED and beeps) | |||||||
| |||||||
Internal Temperature | UPS gives indication of internal temperature, alarm when high temp | ||||||
Event Data Storage |
|
|
| ||||
Applications |
|
|
|
|
|
| |
Switches |
|
| Generator compatible |
| |||
Bypass Switch |
|
|
|
|
|
| |
Bypass Disable | Static switch <1/4 cycle (50Hz: 5 ms/60Hz: 4.16 ms) | ||||||
Automatic Retransfer | Factory or authorized service center selectable only | ||||||
User Interface |
| Provided – Can be disabled from front panel |
| ||||
Real Time Clock |
|
|
|
|
|
| |
Schedule Operation | Standard – Minimum 3 days memory backup during power loss | ||||||
RUN/STOP Disable | Schedule ON/OFF operation of UPS using communication software | ||||||
Autostart | UPS has option for UPS to start automatically when AC is applied | ||||||
Remote ON/OFF |
|
| Standard – External terminal |
| |||
LED Display | 4 LED’s indicating input/output condition, warning and battery operation | ||||||
LCD Screen |
|
| 16 characters x 2 lines |
| |||
UPS Operation: 6 Keys | Run/Stop, Set/Monitor, Shift/Select, Del/(page down), Reset/(page up) | ||||||
Buzzer Volume |
|
| Low, High, Mute; Selectable by keypad |
| |||
Power Connections |
|
| Standard – Hard wire |
| |||
Emergency Power Off |
|
| Standard – Terminal contacts only |
| |||
Remote Contacts |
|
| Standard (INV, BYP, BATT, LB, AC, FLT) |
| |||
RS232 ASCII Interface |
|
| Standard |
|
1.Input/output figures rated for 240 volts. Output ratings given for 0.85PF are only valid when the input voltage is greater than 204 volts; otherwise, ratings given for 0.70PF are applicable.
2.At 6600 ft (2000 m) above sea level, output capacity should be derated by 3%