Toshiba 1600EP Series Preventive Maintenance/Parts Replacement, Batt Amb Temp, Average lifetime

Models: 1600EP Series

1 64
Download 64 pages 52.93 Kb
Page 52
Image 52
Preventive Maintenance/Parts Replacement

Preventive Maintenance/Parts Replacement

Preventive Maintenance

Toshiba 1600EP Series of uninterruptible power systems have been designed to provide years of trouble- free operation requiring a minimum of preventive maintenance.

The best preventive measure that the UPS user can take is to keep the area around the unit, particularly the air inlet vents, clean and free of moisture and dust accumulations. If the atmosphere of the installation site is very dusty, use a vacuum cleaner to periodically remove dust accumulations around and from the unit.

Caution

Only a qualified Toshiba representative should be allowed to perform any routine maintenance or service on this equipment other than those preventive maintenance details which are described directly above this caution.

Parts Replacement

The following list shows recommended intervals for periodic replacement of certain UPS parts:

1.Aluminum electrolytic capacitors: Replace once every 5 years.

2.Fuses: Replace once every 7 years.

3.Cooling fan: When operated in an ambient temperature of 86 °F (30 °C) to 104 °F (40° C), replace every 3.5 years. When operated in an ambient temperature of less than 86 °F (30 °C) , replace every 5 years.

4.Batteries: In order to maintain system reliability, the UPS batteries should be replaced on a regular schedule. To ensure reliable operation, all of the batteries should be replaced at the same time. Use the following chart for replacement:

UPS Battery Replacement

Batt Amb Temp

Average lifetime

(% Reduced)

68 – 77

°F (20

– 25 °C)

Approximately 5 yrs.

0%

86

°F (30

°C)

Approximately 3.5 yrs.

30%

95 °F (35 °C)

Approximately 2.5 yrs.

50%

104 °F (40 °C)

Approximately 1.8 yrs.

66%

113 °F (45 °C)

Approximately 1.25 yrs.

75%

44

1600EP Series Instruction Manual

Page 52
Image 52
Toshiba 1600EP Series manual Preventive Maintenance/Parts Replacement, Batt Amb Temp, Average lifetime, Reduced