Standard Models: 3.6kVA-RoHS; 3.6kVA; 6kVA; 8kVA (cont’d)
Unit (Capacity) | 3.6 |
| 3.6 kVA (3.1 kW)1 | 6 kVA (5.1 kW)1 | 8 kVA (6.8 kW)1 | |||
(3.1 kW)1 |
| |||||||
|
|
|
|
|
|
| ||
Environment |
|
|
|
|
|
|
| |
Operating Temperature |
|
| 60 Hz |
|
|
| 50 Hz | |
59 – 77 °F (15 – 25 °C) | 32 – 104 °F (0 – 40 °C) |
| 32 – 91 °F (0 – 33 °C) | |||||
recommended |
| |||||||
|
|
|
|
|
|
| ||
Storage Temperature |
|
|
| |||||
Installation Area | To be installed in a well ventilated area free of airborne dust, | |||||||
metal particles or flammable gas, allow at least 4 inches on all sides | ||||||||
| ||||||||
Operating Humidity |
|
| 30 – 90% |
| ||||
Altitude |
|
| < 3300 ft. (1000 m) above sea level 2 |
| ||||
Acoustical Noise | 50 dB (A) maximum @ 1 meter from front panel | |||||||
Heat Generation | 1588 BTU/Hr |
| 1588 BTU/Hr | 2610 BTU/Hr |
| 3482 BTU/Hr | ||
Operation Diagnosis |
|
|
|
|
|
|
| |
Battery Check | Performed on start up, by schedule, | |||||||
Input OV Protection |
|
| Standard |
| ||||
Battery Lifetime |
| UPS calculates battery replacement time |
| |||||
based upon battery ambient temperature (LCD display, LED and beeps) | ||||||||
| ||||||||
Internal Temperature | UPS gives indication of internal temperature, alarm when high temp | |||||||
Event Data Storage |
| 64 – Supply Mode, 32 – Backup, 16 – Faults |
| |||||
Applications |
|
|
|
|
|
|
| |
Switches |
|
| Generator compatibility |
| ||||
Bypass Switch |
|
|
|
|
|
|
| |
Bypass Disable | Static switch < ¼ cycle (50 Hz – 5 ms/60 Hz – 4.16 ms) | |||||||
Automatic Retransfer | Factory or authorized service center selectable only | |||||||
User Interface |
| Provided – Can be disabled from front panel |
| |||||
Real Time Clock |
|
|
|
|
|
|
| |
Schedule Operation | Standard – Minimum 3 days memory backup during power loss | |||||||
RUN/STOP Disable | Schedule ON/OFF operation of UPS using communication software | |||||||
Autostart | UPS has option for UPS to start automatically when AC is applied | |||||||
Remote ON/OFF |
|
| Standard – External terminal |
| ||||
LED Display | 4 LED’s indicating input/output condition, warning and battery operation | |||||||
LCD Screen |
|
| 16 characters x 2 lines |
| ||||
UPS Operation: 6 Keys | Run/Stop, Set/Monitor, Shift/Select, Del/Page Down, Reset/Page Up | |||||||
Buzzer Volume |
| Selectable by keypad – Low, High, Mute |
| |||||
Power Connections |
|
| Standard – Hard wire |
| ||||
Emergency Power Off |
|
| Standard – Terminal contacts only |
| ||||
Remote Contacts |
| Standard (INV, BYP, BATT, LB, AC, FLT) |
| |||||
RS232 ASCII Interface |
|
| Standard |
|
1.Input/output figures rated for 240 volts. Output ratings given for 0.85PF are only valid when the input voltage is greater than 204 volts; otherwise, ratings given for 0.70PF are applicable.
2.At 6600 ft (2000 m) above sea level, output capacity should be derated by 3%
16 | 1600EP Series Instruction Manual |