Toshiba 1600EP Series Standard Models 3.6kVA-RoHS 3.6kVA 6kVA 8kVA cont’d, Unit Capacity, 3.1 kW1

Models: 1600EP Series

1 64
Download 64 pages 52.93 Kb
Page 24
Image 24
Standard Models: 3.6kVA-RoHS; 3.6kVA; 6kVA; 8kVA (cont’d)

Standard Models: 3.6kVA-RoHS; 3.6kVA; 6kVA; 8kVA (cont’d)

Unit (Capacity)

3.6 kVA-RoHS

 

3.6 kVA (3.1 kW)1

6 kVA (5.1 kW)1

8 kVA (6.8 kW)1

(3.1 kW)1

 

 

 

 

 

 

 

 

Environment

 

 

 

 

 

 

 

Operating Temperature

 

 

60 Hz

 

 

 

50 Hz

59 – 77 °F (15 – 25 °C)

32 – 104 °F (0 – 40 °C)

 

32 – 91 °F (0 – 33 °C)

recommended

 

 

 

 

 

 

 

 

Storage Temperature

 

 

-4 – 104 °F (-20 – 40 °C)

 

Installation Area

To be installed in a well ventilated area free of airborne dust,

metal particles or flammable gas, allow at least 4 inches on all sides

 

Operating Humidity

 

 

30 – 90% non-condensing

 

Altitude

 

 

< 3300 ft. (1000 m) above sea level 2

 

Acoustical Noise

50 dB (A) maximum @ 1 meter from front panel

Heat Generation

1588 BTU/Hr

 

1588 BTU/Hr

2610 BTU/Hr

 

3482 BTU/Hr

Operation Diagnosis

 

 

 

 

 

 

 

Battery Check

Performed on start up, by schedule, on-demand (user configurable)

Input OV Protection

 

 

Standard

 

Battery Lifetime

 

UPS calculates battery replacement time

 

based upon battery ambient temperature (LCD display, LED and beeps)

 

Internal Temperature

UPS gives indication of internal temperature, alarm when high temp

Event Data Storage

 

64 – Supply Mode, 32 – Backup, 16 – Faults

 

Applications

 

 

 

 

 

 

 

Switches

 

 

Generator compatibility

 

Bypass Switch

 

 

 

 

 

 

 

Bypass Disable

Static switch < ¼ cycle (50 Hz – 5 ms/60 Hz – 4.16 ms)

Automatic Retransfer

Factory or authorized service center selectable only

User Interface

 

Provided – Can be disabled from front panel

 

Real Time Clock

 

 

 

 

 

 

 

Schedule Operation

Standard – Minimum 3 days memory backup during power loss

RUN/STOP Disable

Schedule ON/OFF operation of UPS using communication software

Autostart

UPS has option for UPS to start automatically when AC is applied

Remote ON/OFF

 

 

Standard – External terminal

 

LED Display

4 LED’s indicating input/output condition, warning and battery operation

LCD Screen

 

 

16 characters x 2 lines

 

UPS Operation: 6 Keys

Run/Stop, Set/Monitor, Shift/Select, Del/Page Down, Reset/Page Up

Buzzer Volume

 

Selectable by keypad – Low, High, Mute

 

Power Connections

 

 

Standard – Hard wire

 

Emergency Power Off

 

 

Standard – Terminal contacts only

 

Remote Contacts

 

Standard (INV, BYP, BATT, LB, AC, FLT)

 

RS232 ASCII Interface

 

 

Standard

 

1.Input/output figures rated for 240 volts. Output ratings given for 0.85PF are only valid when the input voltage is greater than 204 volts; otherwise, ratings given for 0.70PF are applicable.

2.At 6600 ft (2000 m) above sea level, output capacity should be derated by 3%

16

1600EP Series Instruction Manual

Page 24
Image 24
Toshiba 1600EP Series manual Standard Models 3.6kVA-RoHS 3.6kVA 6kVA 8kVA cont’d, Unit Capacity, kVA 3.1 kW1, kVA 5.1 kW1