Online Mode

Online Mode

Online Mode (Run operation)

The following illustration shows circuit power flow when the UPS is operating normally in the Online mode. The UPS rectifier, including a boost chopper circuit, converts AC input power to DC power. The boost chopper circuit maintains a constant voltage, with current limiting, for charging the batteries. It also supplies a DC voltage of the proper level to the inverter section. The inverter section generates a high quality sine wave output voltage. The unit’s batteries are always maintained in a constantly charged state when the UPS is in the run operation mode.

Power flow in ONLINE mode for all models

Static-Bypass Mode (Stop operation)

If the UPS unit is severely overloaded or develops an internal fault, power flow is automatically switched from the unit’s main circuit to the bypass circuit. Power flow through the bypass is shown in the following illustration. This change-over occurs automatically in phase in less than 4 milliseconds. The switching period is not long enough to cause interruptions to occur in most loads.

If the power flow is transferred to the bypass circuit because of an overload and that overload condition ends within a specified period of time then the power flow will be transferred back to the Online mode (run operation) automatically.

If the power flow is transferred to the bypass circuit due to an external fault the UPS will shut down power through the bypass to the load and indicate a system fault message.

If the power flow is transferred to the bypass circuit due to an internal fault the UPS will continue to supply power to the load through the bypass and indicate a system fault message (see system fault message DC-OC on page 43).

If the power flow is transferred to the bypass circuit due to an overload condition (see system warning message OL: REDUCE LOAD on page 39 and AUTO RETRANSFER on page 41), then the power flow will automatically transfer from the UPS’s bypass circuit back to the inverter circuit after removing the overload if set to do so (see auto-transfer setting on page 35).

power flow in bypass mode for all models

24