Status Change Indications

Status Change Indications

Warning messages will be displayed when an abnormal operating condition occurs. The following chart shows possible messages.

LCD Message

Meaning/Action

 

 

 

 

Meaning: The UPS has automatically entered

 

 

 

the bypass mode because it detected an output

 

AUTO RETRANSFER

 

current that is larger than the inverter can

 

 

 

normally handle.

 

 

 

 

Action: Remove excess load equipment to

 

 

 

reduce the output current.

 

 

 

 

Meaning: The UPS input frequency is outside of

 

 

 

the ± 1 Hz synchronization frequency tolerance

 

AUTO RETRANSFER

 

of the inverter output frequency.

 

 

 

 

Action: No action is necessary. Unit cannot

 

 

 

switch to bypass mode while the input frequency

 

 

 

is out of tolerance with the output frequency.

 

 

 

Meaning: The battery level has dropped low

 

 

 

(about 90% or less) during operation. Continued

 

 

 

operation in this mode will deplete battery and

 

BATTERY LOW

 

 

 

cause output shut down.

 

 

 

 

 

 

 

 

Action:

Immediately shutdown the

load

 

 

 

 

 

 

equipment in an orderly fashion and then press

 

 

 

the STOP key.

 

 

 

 

Meaning: A start notice is displayed 5 minutes

 

 

 

before starting the UPS when the start timer is

 

TIME TO RUN 4 MIN

 

 

 

set by communication, and continues to display

 

 

 

 

 

 

remaining time during countdown.

 

 

 

 

 

 

 

 

Action: None required

 

 

 

 

Meaning: A stop notice is displayed 5 minutes

 

 

 

before stopping the UPS when the stop timer is

 

TIME TO STOP 10 SEC

 

 

 

set by communication.

 

 

 

 

 

 

 

 

Action: None required.

 

 

 

 

 

 

 

 

Meaning: When the key lock is set or the

 

 

 

timer is

set to start/stop the UPS by

data

 

KEY LOCK: EN

 

communication, pressing the RUN or STOP key

 

 

 

displays this message.

 

 

 

 

Action: None required.

 