The following screens show the setting procedure for setting the data variables. They are accessed from the main Data Setting screens (see page 33) when the shift/select key is pressed:

Bat Test Interval

screen page 33

Cont’d from

data setting

TO BEGIN: SET

OR

BATTERY TEST

INHIBIT

Shift

+

Set

 

 

BATTERY TEST

Select

Monitor

###%

Executes battery test and returns

to Data Setting screens

This parameter has no options to set. A battery test will be performed once the SHIFT + SET button is pressed.

If the BAT TEST INHIBIT message is displayed, it indicates that a battery test has been performed recently. The UPS will not allow frequent bat- tery tests to insure that the batteries remain in a fully charged state.

Cont’d from Buzzer data setting screen page 33

Cont’d from Clear Timer data setting screen page 33

Cont’d from Clear Timer data setting screen page 33

VOLTAGE ADJ: +5

TO ACCEPT: SET

VOLTAGE ADJ: +4

TO ACCEPT: SET

VOLTAGE ADJ: -5

TO ACCEPT: SET

Loops through

eleven possibilities

CLEAR TIMER SET TO ACCEPT: SET

DEFAULT SETTINGS

TO ACCEPT: SET

Shift

Select

Shift

Select

Shift

Select

Shift

Select

Shift

Select

+

+

+

+

+

Set

 

 

 

VOLTAGE ADJ: +5

Monitor

TO CHANGE:SELECT

Set

 

 

 

 

VOLTAGE ADJ: +4

Monitor

TO CHANGE:SELECT

Set

 

 

 

 

VOLTAGE ADJ: -5

Monitor

TO CHANGE:SELECT

Returns to Data Setting screens

(with new value applied)

Set

 

 

 

CLEAR TIMER SET

Monitor

TO CHANGE:SELECT

Executes battery test and returns

to Data Setting screens

Set

 

 

 

DEFAULT SETTINGS

Monitor

TO CHANGE:SELECT

Executes battery test and returns

to Data Setting screens

This parameter allows the user to off- set the output voltage (while the unit is running on-lline) in 1% increments over a range of +/-5% total offset.

Default value is 0%

This parameter has no options to set. Pressing the SHIFT + SET button while this message is displayed will cancel timer settings.

This parameter has no options to set. Pressing the SHIFT + SET but- ton while this message is displayed will reset all variables to their default value.

38

1600EP Series Instruction Manual

Page 46