Product Description
An uninterruptible power system is a system that is installed between the commercial power and the load equipment. The UPS provides steady AC output power during commercial power
During normal operation, the UPS uses commercial AC power. It absorbes all of the high voltage spikes and transients caused by switching and faults, and all of the
If the AC power supplied to the UPS drops below a specified voltage level, the unit’s batteries automatically begin supplying power instead of receiving it. This insures that the loads connected to the UPS continue to receive power with no interruption. When AC input power becomes available again, operation returns to normal. The unit’s batteries begin to recharge so they will be ready for the next power interruption.
Application and Use
Toshiba 1600EP Series of
Output Rating
Toshiba 1600EP Series (208/240V) offers UPS models with the following capacities:
MODEL | Output Capacity @ 240 V | Output kW @ .85PF 240 V |
UE3G2L036C61TRoHS* | 3.6 kVA | 3.1 kW |
UE3G2L036C61T | 3.6 kVA | 3.1 kW |
UE3G2L060C61T | 6 kVA | 5.1 kW |
UE3G2L080C61T | 8 kVA | 6.8 kW |
UE3G2L100C61T | 10 kVA | 8.5 kW |
UE3G2L140C61T | 14 kVA | 11.9 kW |
UE3G2L180C61T | 18 kVA | 15.3 kW |
UE3G2L220C61T | 22 kVA | 18.7 kW |
*UE3G2L036C61TRoHS is RoHS compliant with the batteries being exempt from the directive.
Power Backup
When an electrical power failure occurs, the UPS’s internal batteries automatically supply
Power Conditioning
When commercial power is present, the UPS supplies conditioned power to the load while maintaining its batteries in a charged condition. The UPS protects against the normal, everyday problems associated with heavy use of raw commercial power, including power sags, surges, signal interference, and spikes. This protection keeps
1600EP Series Instruction Manual