Starting the UPS

Starting the UPS

Turn the main circuit breaker (MCCB) on the back of the UPS (see pages 47-48) to the ON position. The breaker should normally remain in the ON position.

Verify that the ON-LINELED on the front panel (see page 32 and 33) lights green. All LED’s on the front panel may light for a moment when the input breaker is turned on. This is normal. The UPS will now be supplying power in the bypass mode.

Stopping the UPS Caution

When running the UPS for the first time or after the power failure backup operation, charge the batteries for at least 24 hours (input breaker on) before operating the connecting load.

Using the UPS without charging the battery shortens the battery backup operation time, which may result in the destruction of data in case of a power failure.

Press RUN key to begin UPS operation (see page 29 for startup screens).

Caution

If the input breaker is turned off while UPS is in the bypass state, the output power stops. Any load devices will lose power.

Ensure that all sensitive loads have been previously shut down.

Stopping the UPS

To stop the UPS press and hold the STOP key approximately 1 second until the ON-LINELED changes from green to off. The UPS is now in the bypass mode.

To completely stop the UPS, turn the input breaker at the back of the UPS to the OFF position.