For UPS’ equipped with buss strip terminals for the A/C INPUT, BYPASS INPUT, A/C OUTPUT and BATTERY connections, Toshiba recommends using the compression lugs listed in Table 11.2, or their equivalent, for cable terminations to be mounted on the bus strips.

See Table 11.3 – Table 11.5 for recommended cable sizes for the 150, 225, and 300 kVA UPS.

TABLE 11.2 RECOMMENDED CRIMP TYPE COMPRESSION LUGS FOR BUS STRIP TERMINALS

Wire Size

Wire

Recommendation

Crimp tool Required

 

Strand

 

 

Burndy type Y35 or Y46

 

Class

Vendor

Cat. No.

Color Key

Die Index

1/0

B

Burndy

YA25

Pink

12 / 348

 

I

Ilsco

CRA-1/OL

Pink

12 / 348

 

B

Burndy

YA25-LB

Black

13

2/0

B

Burndy

YA26

Black

13

 

I

Ilsco

CRA-2/OL

Black

13

 

B

Burndy

YA27-LB

Orange

14 / 101

3/0

B

Burndy

YA-27

Orange

14 / 101

 

I

Ilsco

CRB-3/OL

Orange

14 / 101

 

B

Burndy

YA28-LB

Purple

15

4/0

B

Burndy

YA28

Purple

15

 

I

Ilsco

CRB-4/OL

Purple

15

 

B

Burndy

YA29-LB

Yellow

16

300 MCM

B

Burndy

YA30

White

17 / 298

 

I

Ilsco

CRA-30OL

White

17 / 298

 

B

Burndy

YA32-LB

Red

18 / 324

350 MCM

B

Burndy

YA31L

Red

18

 

I

Ilsco

CRA-350

Red

18

600 MCM

B

Burndy

YA36L

Green

22

 

I

Ilsco

CRA-600

Green

22

TABLE 11.3 RECOMMENDED CABLE SIZE AND FASTENER TORQUE FOR 150 KVA UNIT

Block Number

Cable Size

Recommended Fastener Torque **

1

AWG 4/0 or larger

540 in.-lb. (6.2 kg-m)

2

AWG 4/0 or larger

540 in.-lb. (6.2 kg-m)

3

AWG 4/0 or larger

540 in.-lb. (6.2 kg-m)

4

AWG 4/0 or larger

540 in.-lb. (6.2 kg-m)

5

AWG 4/0 or larger

540 in.-lb. (6.2 kg-m)

6

AWG 4/0 or larger

540 in.-lb. (6.2 kg-m)

7

AWG 4/0 or larger

540 in.-lb. (6.2 kg-m)

8

AWG 4/0 or larger

540 in.-lb. (6.2 kg-m)

9

AWG 4/0 or larger

540 in.-lb. (6.2 kg-m)

10

AWG 4/0 or larger

540 in.-lb. (6.2 kg-m)

11

AWG 4/0 or larger

540 in.-lb. (6.2 kg-m)

*12

Two 300 MCM or larger

540 in.-lb. (6.2 kg-m)

*13

Two 300 MCM or larger

540 in.-lb. (6.2 kg-m)

 

 

 

*One battery string. (Consult factory if using more than one battery string.)

**Fastener torque specified for: 1/2 in. diameter grade 5 steel bolt.

32

G8000 Series Installation and Operation Manual

Page 40
Image 40
Toshiba 300 KW operation manual YA36L, Block Number Cable Size Recommended Fastener Torque