43

G8000 Series Installation and Operation Manual
12 UPS Specications

12.1 General Specication

Terms Specication Remarks
Conforming Standard UL1778-2001 UL, cUL
Ambient Temperature PF = 1.0: 32 – 86 °F (0 – 30 °C)
PF = 0.8: 86 – 104 °F (30 – 40 °C)
Relative Humidity 30% – 90% Non-condensing
Altitude
< 3280 ft. (< 1000 m) Contact Toshiba Technical
Support for installation above
3280 ft. (1000 m)
Audible Noise 68 dB (100/150/225 kVA), 72 dB (300 kVA) 39 in. (1m) away from front
Insulation Resistance 3 MΩ With 500V-Megger
Insulation Breakdown
AC 2 kV – 1 min. Main Circuit
AC 1.5 kV – 1 min. External Interface
AC 500 V – 1 min. Control Circuit

12.2 Mechanical Specication

Nominal Capacity 100 kW:
T80S3K10KK6XS2H
Cabinet Protection
Conformity IEC298 IP20*
Exterior Paint Sherwin Williams, HHT2-7055, 079 Beige Texture
Panel Thickness
FRONT: 1.6 mm (1/16 in.)
BACK/SIDE/TOP: 1.2 mm (3/64 in.)
BOTTOM: 3.2 mm (1/8 in.)
Input/Output
Cabling Entrance BOTTOM
Ground/Control
Wiring Entrance BOTTOM
Outline Dimension
W: 36.8 in. (935 mm)
D: 31.8 in. (808 mm)
H: 79.2 in. (2012 mm)
Unit Weight 1740 lb. (789 kg)
Shipping Weight 1790 lb. (812 kg)
Floor Loading Per
Footprint
2180 lb./ft.2
(10,644 kg/m2)
Clearance
FRONT: 43 7/16 in. (1100 mm)
BACK/SIDE: 0 in. (0 mm)
TOP: 15 3/4 in. (400 mm)
Heat Rejection 34,121 BTU/h
(8598 kcal/h)
*IP20: Foreign objects that are 12 mm (15/32”) or larger are prevented from entering the enclosure of the UPS.