11.3UPS Power Cable Knockout Plates

Cable knockout plates are provided at the bottom of the 100 kVA UPS, and at the top and bottom of the 150/225 kVA UPS. (Older models of the G8000 150/225 kVA UPS do not come equipped with an upper knockout plate.) The recommended hole locations are illustrated in Figure 11.6, 11.7, and 11.8.

The five (5) holes must be punched during installation. The dashed rectangle indicates the UPS opening behind the knockout plates.

PLATE #1

PLATE #2

0.8”

3” Dia.

0.8”

2” Dia.

AC INPUT

BYPASS AC OUTPUT BATTERY

CONTROL

 

 

WIRES

FIGURE 11.6 - BOTTOM CABLE KNOCKOUT PLATES FOR 100 KVA (T80S3K10KK6XS2H)

PLATE #1

PLATE #2

PLATE #3

0.8”

 

4” Dia.

 

2” Dia.

 

0.4”

 

 

AC INPUT

BYPASS

AC OUTPUT

BATTERY CONTROL

 

 

 

WIRES

FIGURE 11.7 - BOTTOM CABLE KNOCKOUT PLATES 100 KVA (T80S3K10KK6XSNH); 150/225 KVA

4” Dia.

FIGURE 11.8 - TOP ACCESS KNOCKOUT PLATE (IF AVAILABLE - 150 AND 225 KVA ONLY)

34

G8000 Series Installation and Operation Manual

Page 42
Image 42
Toshiba 300 KW operation manual UPS Power Cable Knockout Plates, Bottom Cable Knockout Plates for 100 KVA T80S3K10KK6XS2H