14.7Changing Between Float Charge and Equalize Charge

The procedure to change the recharge mode between float charge and equalize charge is shown in Steps 1-3.

See the Note below for an explanation of Float and Equalize charge modes.

LED Key

- LED Off

- LED On

- LED Flash

UPS SUPPLY

AC - Vo 480 V

AC - Io 50%

STEP 1

Make sure that the FLOAT CHARGE LED is “ON”.

AC INPUT

BATTERIES

BYPASS INPUT

CONVERTER

FLOAT CHARGE

EQUAL CHARGE

DISCHARGE

UPS

INVERTER

AC

SWITCH

BYPASS

AC OUTPUT

UPS SUPPLY

AC - Vo 480 V

AC - Io 50%

STEP 2

Press FLOAT/EQUAL button for at least 0.5 sec.

Change completed.

AC INPUT

BATTERIES

BYPASS INPUT

CONVERTER

FLOAT CHARGE

EQUAL CHARGE

DISCHARGE

UPS

INVERTER

AC

SWITCH

BYPASS

EQUAL CHARGE LED is “ON”.

FLOAT CHARGE LED is “OFF”

AC OUTPUT

STEP 3

 

Please wait until procedure is completed.

NOTE

In equalize charge mode, the battery is charged for a programmed period at a specified voltage (depending on the battery spec), rather than the float charge, in order to prevent voltage deviations among battery cells. This should be done once every six months if possible.

The G8000 UPS will automatically perform the equalize recharge after battery backup operation.