Toshiba 300 KW operation manual Bus Number Cable Size Recommended Fastener Torque

Models: 300 KW

1 80
Download 80 pages 10.03 Kb
Page 41
Image 41

TABLE 11.4 RECOMMENDED CABLE SIZE AND FASTENER TORQUE FOR 225 KVA UNIT

Block Number

Cable Size

Recommended Fastener Torque **

1

Two AWG 2/0 or larger

540 in.-lb. (6.2 kg-m)

2

Two AWG 2/0 or larger

540 in.-lb. (6.2 kg-m)

3

Two AWG 2/0 or larger

540 in.-lb. (6.2 kg-m)

4

Two AWG 2/0 or larger

540 in.-lb. (6.2 kg-m)

5

Two AWG 2/0 or larger

540 in.-lb. (6.2 kg-m)

6

Two AWG 2/0 or larger

540 in.-lb. (6.2 kg-m)

7

Two AWG 2/0 or larger

540 in.-lb. (6.2 kg-m)

8

Two AWG 2/0 or larger

540 in.-lb. (6.2 kg-m)

9

Two AWG 2/0 or larger

540 in.-lb. (6.2 kg-m)

10

Two AWG 2/0 or larger

540 in.-lb. (6.2 kg-m)

11

Two AWG 2/0 or larger

540 in.-lb. (6.2 kg-m)

*12

Three AWG 4/0 or larger

540 in.-lb. (6.2 kg-m)

*13

Three AWG 4/0 or larger

540 in.-lb. (6.2 kg-m)

*One battery string. (Consult factory if using more than one battery string.)

**Fastener torque specified for: 1/2 in. diameter grade 5 steel bolt.

TABLE 11.5 RECOMMENDED CABLE SIZE AND FASTENER TORQUE FOR 300 KVA UPS

Bus Number

Cable Size

Recommended Fastener Torque **

1

Two AWG 4/0 or larger

540 in.-lb. (6.2 kg-m)

2

Two AWG 4/0 or larger

540 in.-lb. (6.2 kg-m)

3

Two AWG 4/0 or larger

540 in.-lb. (6.2 kg-m)

*4

Three 350 MCM or larger

540 in.-lb. (6.2 kg-m)

*5

Three 350 MCM or larger

540 in.-lb. (6.2 kg-m)

6

Two AWG 4/0 or larger

540 in.-lb. (6.2 kg-m)

7

Two AWG 4/0 or larger

540 in.-lb. (6.2 kg-m)

8

Two AWG 4/0 or larger

540 in.-lb. (6.2 kg-m)

9

Two AWG 4/0 or larger

540 in.-lb. (6.2 kg-m)

10

Two AWG 4/0 or larger

540 in.-lb. (6.2 kg-m)

11

Two AWG 4/0 or larger

540 in.-lb. (6.2 kg-m)

12

Two AWG 4/0 or larger

540 in.-lb. (6.2 kg-m)

*One battery string. (Consult factory if using more than one battery string.)

**Fastener torque specified for: 1/2 in. diameter grade 5 steel bolt.

G8000 Series Installation and Operation Manual

33

Page 41
Image 41
Toshiba 300 KW operation manual Bus Number Cable Size Recommended Fastener Torque