12.3Electrical Specification

WARNING

DO NOT open the front cover.

Electric shock, burns or other personal injuries may occur if untrained personnel open the front cover.

Nominal Capacity

100 kW

150 kW

225 kW

300 kW

AC Input Rated Capacity*

110 kW (120 kW)

165 kW (180 kW)

245 kW (270 kW)

320 kW (320 kW)

Input Voltage

 

480 V ( +10% to -15% ), 3-Phase 3-Wire

 

Input Frequency

 

60 Hz ±5%

 

Input Power Factor

 

0.95 – 1.00 Lagging ( at 100% Load )

 

Current Harmonic Distortion

 

4% Maximum ( at 100% Load )

 

Input Capacity Required*

111 kVA (124 kVA)

166 kVA (184 kVA)

250 kVA (274 kVA)

327 kVA (332 kVA)

Circuit Breaker Rating At 480 V

200 A Trip

300 A Trip

450 A Trip

500 A Trip

Input

 

 

 

 

 

* Capacity: Normal Mode (Recharge Mode)

 

Nominal Capacity

100 kW

150 kW

225 kW

300 kW

DC Input Voltage Window

 

288 – 414 VDC

 

Recharge Voltage Regulation

 

± 1.5%

 

 

 

 

 

 

Nominal Capacity

100 kW

150 kW

225 kW

300 kW

AC Output Rated Capacity*

100 kVA (100 kW)

150 kVA (150 kW)

225 kVA (225 kW)

300 kVA (300 kW)

Output Voltage

 

480/277 V ± 1%, 3-Phase 4-Wire

 

Output Power Factor

 

1.0 PF: 32 – 86 °F (0 – 30 °C)

 

 

 

0.8 PF: 86 – 104 °F (30 – 40 °C)

 

Voltage Distortion

3% with 100% Linear Load / 5% with Non-Linear Load

Transient Voltage Regulation

 

< ± 2%

 

Transient Settling Time

 

< 50 ms

 

Crest Factor

 

2.0

 

Output Frequency

 

60 Hz ± 0.01% ( at Free-running Mode)

 

Synchronous Window To Utility Line

 

59 Hz – 61 Hz

 

Frequency Slew Rate

 

1 Hz/Sec

 

Over Load Rating

100% – Continuous / 125% – 10 min. / 150% – 1 min.

* Capacity: Normal Mode (Recharge Mode)

G8000 Series Installation and Operation Manual

45