G8000 Series Installation and Operation Manual
12.3 Electrical Specication
Nominal Capacity 100 kW 150 kW 225 kW 300 kW
AC Input Rated Capacity* 110 kW (120 kW) 165 kW (180 kW) 245 kW (270 kW) 320 kW (320 kW)
Input Voltage 480 V ( +10% to -15% ), 3-Phase 3-Wire
Input Frequency 60 Hz ±5%
Input Power Factor 0.95 – 1.00 Lagging ( at 100% Load )
Current Harmonic Distortion 4% Maximum ( at 100% Load )
Input Capacity Required* 111 kVA (124 kVA) 166 kVA (184 kVA) 250 kVA (274 kVA) 327 kVA (332 kVA)
Circuit Breaker Rating At 480 V
Input
200 A Trip 300 A Trip 450 A Trip 500 A Trip
* Capacity: Normal Mode (Recharge Mode)
Nominal Capacity 100 kW 150 kW 225 kW 300 kW
DC Input Voltage Window 288 – 414 VDC
Recharge Voltage Regulation ± 1.5%
Nominal Capacity 100 kW 150 kW 225 kW 300 kW
AC Output Rated Capacity* 100 kVA (100 kW) 150 kVA (150 kW) 225 kVA (225 kW) 300 kVA (300 kW)
Output Voltage 480/277 V ± 1%, 3-Phase 4-Wire
Output Power Factor 1.0 PF: 32 – 86 °F (0 – 30 °C)
0.8 PF: 86 – 104 °F (30 – 40 °C)
Voltage Distortion 3% with 100% Linear Load / 5% with Non-Linear Load
Transient Voltage Regulation < ± 2%
Transient Settling Time < 50 ms
Crest Factor 2.0
Output Frequency 60 Hz ± 0.01% ( at Free-running Mode)
Synchronous Window To Utility Line 59 Hz – 61 Hz
Frequency Slew Rate 1 Hz/Sec
Over Load Rating 100% – Continuous / 125% – 10 min. / 150% – 1 min.
* Capacity: Normal Mode (Recharge Mode)