MEASUREMENT SCREENS
O/P CURRENT (PEAK)
TABLE 13.2 - CONTINUED
Shows the peak output current peak (%) for each phase.
U50[%]
V50[%]
W50[%]
Peak value of output current
RMS value for rated current x 1.41
x 100 [%]
AC INPUT
AC I/P-V 480[V]
FREQ. 60.0[Hz]
BYPASS INPUT
BYP I/P-V 480[V]
FREQ. 60.0[Hz]
Shows the AC Input Voltage
Shows the Bypass Input Voltage
BATTERY
DISCHARGING 15[MIN]
Shows the remaining battery backup time with rated load and cumulative discharged time.
DC INPUT
DC-V 632[V]
BATT-V 400[V]
BATT- I 0[A]
MODE COUNT
UPS 35[H] BATTERY 56[MIN]
32[TIM]
CLOCK
TIME 03-24-06 13:58
Shows the internal DC bus voltage, battery voltage and battery current.
The battery current value displayed is negative during recharge and positive during discharge.
Shows the cumulative UPS operation time, the cumulative battery backup time and the number of battery backup operations.
The current time is displayed if there are no faults recorded, or after the reset button is pressed.
Date is displayed in the
Time is displayed in the
G8000 Series Installation and Operation Manual | 51 |