Toshiba 300 KW operation manual Nominal Capacity 150 kW 225 kW 300 kW

Models: 300 KW

1 80
Download 80 pages 10.03 Kb
Page 52
Image 52

12.2Mechanical Specification (cont.)

Nominal Capacity

150 kW

 

225 kW

300 kW

Cabinet Protection

 

 

IEC298 IP20*

 

Conformity

 

 

 

 

 

 

 

Exterior Paint

Sherwin Williams, HHT2-7055, 079 Beige Texture

 

 

 

FRONT: 1/16 in. (1.6 mm)

Panel Thickness

BACK/SIDE/TOP: 3/64 in. (1.2 mm)

 

 

 

BOTTOM: 1/8 in. (3.2 mm)

Input/Output

TOP and BOTTOM

TOP

Cabling Entrance

 

 

 

 

Ground/Control

TOP and BOTTOM

TOP

Wiring Entrance

 

 

 

 

 

W: 55.1 in. (1400 mm)

W: 76.8 in. (1951 mm)

Outline Dimension

D: 31.8 in. (808 mm)

D: 31.8 in. (808 mm)

 

H: 79.2 in. (2012 mm)

H: 79.4 in. (2017 mm)

Unit Weight

2467 lbs (1119 kg)

 

2980 lbs (1352 kg)

4575 lbs (2075 kg)

Shipping Weight

2556 lbs (1159 kg)

 

3069 lbs (1392 kg)

4725 lbs (2143 kg)

Floor Loading Per

3280 lbs/ft2

 

3733 lbs/ft2

2460 lbs/ft2

Footprint

(16,014 kg/m2)

 

(18,226 kg/m2)

(12,011 kg/m2)

 

 

FRONT: 43 7/16 in. (1100 mm)

Clearance

 

 

BACK/SIDE: 0 in. (0 mm)

 

 

 

TOP: 15 3/4 in. (400 mm)

Heat Rejection

51,182 BTU/h

 

68,243 BTU/h

68,243 BTU/h

(12,897 kcal/h)

 

(17,197 kcal/h)

(17,197 kcal/h)

 

 

*IP20: Foreign objects that are 12 mm (15/32 in.) or larger are prevented from entering the enclosure of the UPS.

44

G8000 Series Installation and Operation Manual

Page 52
Image 52
Toshiba 300 KW operation manual Nominal Capacity 150 kW 225 kW 300 kW