Step 4-5 continues the procedure to start the UPS.

LED Key

- LED Off

- LED On

- LED Flash

BYPASS

MOVE 72B TO ‘ON’ POSITION

STEP 4

Turn on the DC Input Breaker (72B) on the external battery cabinet.

BATTERIES LED is “ON”.

AC INPUT

BATTERIES

BYPASS INPUT

CONVERTER

FLOAT CHARGE

EQUAL CHARGE

DISCHARGE

UPS

INVERTER

AC

 

SWITCH

AC OUTPUT

 

BYPASS

 

UPS SUPPLY

AC - Vo 480 V

AC - Io 50%

STEP 5

*Press the “UPS” button for at least 0.5 seconds. This completes UPS startup procedure

AC INPUT

BATTERIES

BYPASS INPUT

CONVERTER

FLOAT CHARGE

EQUAL CHARGE

DISCHARGE

UPS

INVERTER

AC

SWITCH

BYPASS

BYPASS LED is “OFF”.

UPS LED is “ON”.

AC OUTPUT

NOTE

*If the AC switch does not function, contact Toshiba or authorized representatives.

If the bypass power source is out of specification, this operation will be inhibited. In order to switch manually, press the “UPS” button for 5 seconds or more.

G8000 Series Installation and Operation Manual

57