11.7.4Grounding Configuration (with corner-grounded delta-input)
If one phase of
The jumper cable should be removed see Figure 11.13 for the jumper cable location.
During normal operation the UPS output is floating relative to the ground. An isolation transformer is recommended at output distribution as shown in Figure 11.16.
Input Source | < UPS Cabinet > |
|
3φ 3φ
Bφ N
3φ 3φ
GG
Output Distribution
3φ 3φ
3φ | N | To the |
| ||
N |
| Load |
|
| |
G | G |
|
Remove
Jumper Cable
FIGURE 11.16 - GROUNDING CONFIGURATION WITH CORNER-GROUNDED DELTA-INPUT.