20 Analog I/O Modules (AD268 / DA264 / TC218)
5. I/O Allocation and Programming PART 1 AD268
0 to 10V range:
A/D conversion data
Input voltage Hex adecimal Integer Resolution
Upper limit +10.2 V H7F80 32640
:: :
Full scale (positive) +10 V H7D00 32000
:: :
+0.3125 mV H0001 1
0 0 V H0000 0
0.3125 mV / bit
D = 3200 × A
D: Digital data
A: Analog signal (V)
0
H3FFF
16383
Analog input
+5.1196V
Digital value
+10.2V
H7D00
32000
-10.2V
+10
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net