Users Manual 65
PART 3 TC218 3. Input Type Setting
3.2 Parameter setting by software
The input type of the TC218 is specified by writing the following parameter data into the
TC218's buffer memory. To access the buffer memory, T2 user program (READ and WRITE
instructions) is required.
When the parameter is set to the TC218, it is saved in the TC218's built-in EEPROM.
Therefore, once the input type parameter is set, there is no need to execute the input type
setting operation.
T2 CPU TC218
Input type parameter data:
Parameter
data Input type
0 Type K thermocoupl e
1 Type J thermocoupl e
2 Type E thermocoupl e
5±100mV
TC218 buffer memory address:
H8018 Input type for channel 1
H8019 Input type for channel 2
H801A Input type for channel 3
H801B Input type for channel 4
H801C I nput type for channel 5
H801D I nput type for channel 6
H801E Input type for channel 7
H801F Input type for channel 8
Set the same parameter data for all 8 channels.
The factory setting is ±100mV range.
For details of the procedure to set the input type parameter, refer to section 6.
Buffer memory
User program
WRITE
READ
EEPROM